IFP-2000 Installation Manual
11-4
151430
Auxiliary power trouble restore
pi Exp. ID
FJ
Point #
FJNNXXPPPP
3
320
Exp. ID
Point #
Detector alarm
pi Exp. ID
FA
Point #
FANNXXPPPP
1
110
Exp. ID
Point #
Detector alarm restore
pi Exp. ID
FH
Point #
FHNNXXPPPP
3
110
Exp. ID
Point #
Detector disabled
pi Exp. ID
FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Detector enabled
pi Exp. ID
FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Detector trouble
pi Exp. ID
FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Detector trouble restore
pi Exp. ID
FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
External Reset/Silence/Fire Drill switch disabled
pi Exp. ID
FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
External Reset/Silence/Fire Drill switch enabled
pi Exp. ID
FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
External Reset/Silence/Fire Drill switch trouble
pi Exp. ID
UT
Point #
UTNNXXPPPP
1
373
Exp. ID
Point #
External Reset/Silence/Fire Drill switch trouble restore
pi Exp. ID
UJ
Point #
UJNNXXPPPP
3
373
Exp. ID
Point #
Interlock switch alarm (Water Release Zone)
pi Exp. ID
FA
Point #
FANNXXPPPP
1
110
Exp. ID
Point #
Interlock switch alarm restore (Water Release Zone)
pi Exp. ID
FH
Point #
FHNNXXPPPP
3
110
Exp. ID
Point #
Interlock switch disabled
pi Exp. ID
FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Interlock switch enabled
pi Exp. ID
FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Interlock switch trouble (Water Release Zone)
pi Exp. ID
FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Interlock switch trouble restore (Water Release Zone)
pi Exp. ID
FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
Manual pull switch alarm
pi Exp. ID
FA
Point #
FANNXXPPPP
1
115
Exp. ID
Point #
Manual pull switch alarm restore
pi Exp. ID
FH
Point #
FHNNXXPPPP
3
115
Exp. ID
Point #
Manual pull switch disabled
pi Exp. ID
FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Manual pull switch enabled
pi Exp. ID
FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Manual pull switch trouble
pi Exp. ID
FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Manual pull switch trouble restore
pi Exp. ID
FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
Manual release switch alarm (Water Release Zone)
pi Exp. ID
FA
Point #
FANNXXPPPP
1
110
Exp. ID
Point #
Manual release switch alarm restore (Water Release Zone)
pi Exp. ID
FH
Point #
FHNNXXPPPP
3
110
Exp. ID
Point #
Manual release switch disabled
pi Exp. ID
FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Manual release switch enabled
pi Exp. ID
FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Manual release switch trouble (Water Release Zone)
pi Exp. ID
FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Manual release switch trouble restore (Water Release Zone)
pi Exp. ID
FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
Notification output point disabled
pi Exp. ID
FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Notification output point enabled
pi Exp. ID
FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Notification output point trouble
pi Exp. ID
FT
Point #
FTNNXXPPPP
1
320
Exp. ID
Point #
Notification output point trouble restore
pi Exp. ID
FJ
Point #
FJNNXXPPPP
3
320
Exp. ID
Point #
Positive Alarm Sequence acknowledge switch disabled
pi Exp. ID
FB
Point #
FBNNXXPPPP
1
571
Exp. ID
Point #
Positive Alarm Sequence acknowledge switch enabled
pi Exp. ID
FU
Point #
FUNNXXPPPP
3
571
Exp. ID
Point #
Positive Alarm Sequence acknowledge switch trouble
pi Exp. ID
FT
Point #
FTNNXXPPPP
1
373
Exp. ID
Point #
Positive Alarm Sequence acknowledge switch trouble restore
pi Exp. ID
FJ
Point #
FJNNXXPPPP
3
373
Exp. ID
Point #
Supervisory/Tamper alarm condition
pi Exp. ID
SS
Point #
SSNNXXPPPP
1
203
Exp. ID
Point #
Supervisory/Tamper alarm condition restore
pi Exp. ID
SR
Point #
SRNNXXPPPP
3
203
Exp. ID
Point #
Supervisory/Tamper point disabled
pi Exp. ID
SB
Point #
SBNNXXPPPP
1
571
Exp. ID
Point #
Supervisory/Tamper point enabled
pi Exp. ID
SU
Point #
SUNNXXPPPP
3
571
Exp. ID
Point #
Supervisory/Tamper point trouble
pi Exp. ID
ST
Point #
STNNXXPPPP
1
373
Exp. ID
Point #
Supervisory/Tamper point trouble restore
pi Exp. ID
SJ
Point #
SJNNXXPPPP
3
373
Exp. ID
Point #
System-based AUX1 switch alarm
pi Exp. ID
UA
Point #
UANNXXPPPP
1
140
Exp. ID
Point #
System-based AUX1 switch alarm restore
pi Exp. ID
UH
Point #
UHNNXXPPPP
3
140
Exp. ID
Point #
System-based AUX1 switch disabled
pi Exp. ID
UB
Point #
UBNNXXPPPP
1
571
Exp. ID
Point #
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier (same as IFP-1000 Rev 9)
SIA IFP-2000
Event Description
Module ID #
(If Any)
SIA Event
Codes
Parameter
Fixed Length Format
NN - panel ID
XX - SBUS ID
ZZZ - zone #
PPPP - Point #
AAAAAA-account #
Qualifier
Event
Code
Group #
Contact #
Содержание IFP-2000
Страница 2: ......
Страница 12: ...IFP 2000 Installation Manual viii...
Страница 22: ...IFP 2000 Installation Manual 1 10 151430...
Страница 26: ...IFP 2000 Installation Manual 2 4 151430...
Страница 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example...
Страница 100: ...IFP 2000 Installation Manual 5 14 151430...
Страница 124: ...IFP 2000 Installation Manual 8 8 151430 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 125: ...Programming Overview 151430 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 194: ...IFP 2000 Installation Manual 10 20 151430...
Страница 210: ...IFP 2000 Installation Manual 12 8 151430...
Страница 215: ...Installation Records 151430 13 5 Module Addr Zone Group Description Module Addr Zone Group Description...
Страница 230: ...IFP 2000 Installation Manual A 14...
Страница 232: ...IFP 2000 Installation Manual B 2 151430...
Страница 236: ......
Страница 237: ......