Programming Overview
151430
8-3
7. Select one of the following options from the menu that displays.
- Review System
Press
if you need to review the JumpStart configuration.
- Repeat JumpStart
Press
if you need to rerun JumpStart for any reason.
- Accept Changes
1. If you are ready to make the JumpStart configuration permanent, select
.
2. The system will ask you if the installation contains duct detectors. If there
are none, select
for No and skip to Step 8. If the system contains duct
detectors, select
for Yes and continue with Step 3.
3. From the list that displays, select the 5815XL device that contains the duct
detectors.
4. The first photoelectric or ionization detector on the system will display.
Select
for DUCT and
for NonDUCT.
5. Press
to select the next detector. Select
for DUCT and
for Non-
DUCT. Continue until all duct detectors have been selected. (Note: You can
move backwards through the list with
).
6. When you reach the last detector on this device, press
.
7. The system will ask you if there are more duct detectors in the system. If
there are, select
for Yes and repeat from Step 3. If there are no more
duct detectors, select
for No and continue with Step 8.
8. The system will restart in 10 seconds. You can press
to restart immedi-
ately. Do not select
for System Diagnostics. (This feature is for use in
testing at the factory).
9. After the system resets, it will use the new JumpStart configuration.
- Discard Changes
If you want to discard the changes, and keep the configuration you had before
running this JumpStart press
.
1
1
2
2
3
3
2
1
1
2
1
2
1
2
1
2
4
4
Содержание IFP-2000
Страница 2: ......
Страница 12: ...IFP 2000 Installation Manual viii...
Страница 22: ...IFP 2000 Installation Manual 1 10 151430...
Страница 26: ...IFP 2000 Installation Manual 2 4 151430...
Страница 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example...
Страница 100: ...IFP 2000 Installation Manual 5 14 151430...
Страница 124: ...IFP 2000 Installation Manual 8 8 151430 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 125: ...Programming Overview 151430 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 194: ...IFP 2000 Installation Manual 10 20 151430...
Страница 210: ...IFP 2000 Installation Manual 12 8 151430...
Страница 215: ...Installation Records 151430 13 5 Module Addr Zone Group Description Module Addr Zone Group Description...
Страница 230: ...IFP 2000 Installation Manual A 14...
Страница 232: ...IFP 2000 Installation Manual B 2 151430...
Страница 236: ......
Страница 237: ......