IFP-2000 Installation Manual
9-8
151430
Smoke Detector Sensitivity
All detectors in the zone will respond as programmed in this menu location.
* Automatic drift compensation is always in effect for all detectors. Detectors are sampled every 3 hours. See Section 10.4.11
for information about how to check if a detector is in compliance.
6. Use the
or
keys to scroll through the range or enter directly from the number keys
on the annunciator.
7. Then press
.
9.3.1.3 Zone Accessory Options
Single or Multi-station cadence pattern (choose from Patterns 00 to 22).
Local Zone (choose Y or N, for Yes or No).
9.3.2
Add Zone
To add a zone, follow these steps:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
Display reads:
Initializing
Please wait . . .
3. Press
to enter zone menu.
4. Press
to add a zone.
A zone will be added. The system will assign the next available zone number. Options for
IMPORTANT!
Drift compensation is automatic for all smoke detectors (photoelectric and ionization). The feature is always in effect, no
programming is required. See Section 10.4.11 for information about how to check if a detector is in UL compliance.
Detector
Protocol
Type of Smoke
Detector
Choices
Comments
IDP
IDP-Photo,
IDP-Acclimate, &
IDP-Photo-T
Low (3.5% obscurity)
If the day/night sensitivity option is selected, you can have
different sensitivity settings during the day and at night. You
can determine the days of the week that Day/Night Sensitivity
will automatically adjust. You can also designate specific days
as Holidays. Holiday and weekend days use night sensitivity
for the entire day
Medium (2.5% obscurity)
High (1.5% obscurity)
IDP-Ion
Low (55 pA)
Medium (68 pA)
High (80 pA)
IDP-Pduct &
IDP-Pduct-R
Low (2.5% obscurity)
Medium (2.0% obscurity)
High (1.5% obscurity)
7
2
2
Содержание IFP-2000
Страница 2: ......
Страница 12: ...IFP 2000 Installation Manual viii...
Страница 22: ...IFP 2000 Installation Manual 1 10 151430...
Страница 26: ...IFP 2000 Installation Manual 2 4 151430...
Страница 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example...
Страница 100: ...IFP 2000 Installation Manual 5 14 151430...
Страница 124: ...IFP 2000 Installation Manual 8 8 151430 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 125: ...Programming Overview 151430 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 194: ...IFP 2000 Installation Manual 10 20 151430...
Страница 210: ...IFP 2000 Installation Manual 12 8 151430...
Страница 215: ...Installation Records 151430 13 5 Module Addr Zone Group Description Module Addr Zone Group Description...
Страница 230: ...IFP 2000 Installation Manual A 14...
Страница 232: ...IFP 2000 Installation Manual B 2 151430...
Страница 236: ......
Страница 237: ......