Section 3
Installation
This section contains information necessary to install the 5104 Fire Communicator and accessories.
3.1
Electrical Specifications
3.2
Environmental Specifications
It is important to protect the 5104 panel from water. To prevent water damage, the following precautions should
be FOLLOWED when mounting the unit:
•
Mount indoors in dry locations only
•
Do not mount directly on exterior walls, especially masonry walls (condensation).
•
Do not mount directly on exterior walls below grade (condensation).
•
Protect from plumbing leaks.
•
Protect from splash caused by sprinkler system inspection ports.
•
Do not mount in areas with humidity-generating equipment (such as dryers, production machinery, etc.).
•
Operating temperature range is 32° to 120° F (0° to 49° C).
•
Indoor use only.
•
10% to 93% non-condensing humidity at 30°C (86°F).
•
Non-corrosive environment.
Primary AC
120 Vrms @ 60Hz, 374 ma
Total DC load
1.3 Amp
Accessory Power
12 VDC @ 750 mA
Phone Line Voltage
2.75 VDC min.
Smoke Power
12 VDC @ 750 mA
Battery Charging Voltage
13.8 VDC
Minimum Low Battery Detection
10.2 VDC
Minimum Low AC Detection
102 Vrms @ 60 Hz, full load
Auxiliary Notification Appliance Circuit
12 VDC @ 500 mA