SILENT KNIGHT 5104B Скачать руководство пользователя страница 2

Installation Procedure

Adherence to the following will aid in problem-free installation with long-term reliability:

Installation Precautions

 - Adherence to the following will aid in problem-free installation with long-term reliability: 

WARNING

 - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources 

of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, 
modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until 
manuals are read and understood. 

CAUTION

 - System Re-acceptance Test after Software Changes: To ensure proper 

system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in 
site-specific software. Re-acceptance testing is required after any change, addition or deletion of system components, or 
after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or 
software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are 
not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum 
of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for 
operation within the range of 0°C-49°C (32°F-120°F) or humidity within the range of 10%-93% at 30°C (86°F) non-
condensing. However, the useful life of the system's standby batteries and the electronic components may be adversely 
affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be 
installed in an environment with a normal room temperature of 15-27º C/60-80º F. 

Verify that wire sizes are adequate

 for 

all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device 
voltage. 

Like all solid state electronic devices

, this system may operate erratically or can be damaged when subjected to 

lightning induced transients. Although no system is completely immune from lightning transients and interference, proper 
grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased 
susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated 
or encountered. 

Disconnect AC power and batteries

 prior to removing or inserting circuit boards. Failure to do so can 

damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. 
When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not 
interfere with battery, transformer, or printed circuit board location. 

Do not tighten screw terminals

 more than 9 in-lbs. 

Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal 
removal. fire alarm control panels contain static-sensitive components. Always ground yourself with a proper wrist strap 
before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect 
electronic assemblies removed from the unit.

Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to 
avoid damage to the control panel and associated equipment. Fire Alarm Control Panel (FACP) operation and reliability 
depend upon proper installation.

While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance! 

An 

automatic fire alarm system

 - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning 

devices, and a fire alarm control with remote notification capability - can provide early warning of a developing fire. Such 
a system, however, does not assure protection against property damage or loss of life resulting from a fire. 

Any fire alarm 

system

 may fail for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such 

as in chimneys, in walls, or roofs, or on the other side of closed doors. 

Smoke detectors

 also may not sense a fire on 

another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire. 
Furthermore, all types of smoke detectors, including ionization and photoelectric types, have sensing limitations. No type 
of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent 
explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with 
matches, or arson.

IMPORTANT! Smoke detectors must

 be installed in the same room as the control panel and in rooms used by the 

system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so 
located, a developing fire may damage the alarm system, crippling its ability to report a fire. 

Audible warning devices

 

such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located 
on another floor of a building. 

A fire alarm system

 will not operate without any electrical power. If AC power fails, the 

system will operate from standby batteries only for a specified time. 

Rate-of-Rise heat detectors

 may be subject to 

reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per 
year by a qualified fire protection specialist. 

Equipment used in the system

 may not be technically compatible with the 

control. It is essential to use only equipment listed for service with your control panel. 

Telephone lines

 needed to transmit 

alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. 

The most 

common cause

 of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be 

tested and maintained by professional fire alarm installers following written procedures supplied with each device. System 
inspection and testing should be scheduled monthly or as required by national and/or local fire codes. Adequate written 
records of all inspections should be kept.

Содержание 5104B

Страница 1: ...Installation and Operations Manual Model 5104B Fire Communicator Document 151053 L8 05 05 2014 Rev F3 P N 151053 L8 F3 ECN 14 0068...

Страница 2: ...itive components Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic a...

Страница 3: ...ator LEDs L6 L7 3 5 3 4 2 3 Overcurrent LED Indicators L1 L2 3 6 3 4 3 Reset Silence Switch 3 6 3 4 4 Cable Connectors P1 P2 and P3 3 6 3 4 5 On board Piezo Sounder 3 6 3 5 Calculating Current Draw an...

Страница 4: ...ts 6 1 6 2 5230 Programming 6 1 6 2 1 Default User Codes 6 1 6 2 2 How to Enter and Exit Program Mode 6 1 6 2 3 How to Enter Program Mode 6 2 6 2 4 How to Exit Program Mode 6 2 6 2 5 Step Programming...

Страница 5: ...mmable relay output provides additional annunciation for either alarm or dialer failed condition Three LEDs indicating AC power green status Trouble Silenced yellow and Dialer Failed yellow Four LEDs...

Страница 6: ...d to be performed Please let us know if the manual does not meet your needs in any way 1 3 1 How to Use This Manual In this manual the following conventions are used Pages of the manual are numbered b...

Страница 7: ...number and then return it to Silent Knight 12 Clintonville Road Northford CT 06472 1610 800 328 0103 or 203 484 7161 If the Model 5104 causes harm to the telephone network the telephone company will n...

Страница 8: ...d ensure that it is permissible for the equipment to be connected to the facilities of the local telecommunications company In some cases the company s inside wiring associated with a single line indi...

Страница 9: ...rior walls below grade condensation Protect from plumbing leaks Protect from splash caused by sprinkler system inspection ports Do not mount in areas with humidity generating equipment such as dryers...

Страница 10: ...stance as possible or use shielded cable Connect the shield to earth ground at the panel only High frequency noise such as that produced by the inductive reactance of a speaker or bell can also be red...

Страница 11: ...describes the 5104 board components including terminal strips LEDs Switches and cable connectors See Figure 3 2 Figure 3 2 5104 Circuit Board Terminal Block 1 Terminal Block 3 Terminal Block 2 P1 P2...

Страница 12: ...Limited 0 7 Circuit Ground 0 8 Input Class B Style A Zone 3 0 9 Power Power Limited 0 10 Input Class B Style A Zone 4 0 11 Power Power Limited 0 12 Circuit Ground 0 2 13 Telco Ring Phone Line 1 N A 1...

Страница 13: ...eans that any time the control panel dialer needs to communicate with the central station it will not be possible to use the tele phones that are on the same line as the fire system During communicati...

Страница 14: ...devices depress the reset silence switch for a minimum of 1 second The Reset Silence switch is accessible inside the panel DO NOT install the switch extender provided with the system for UL certified...

Страница 15: ...line A 3 Add up the current draw for all the smoke detectors and record the totals in line B 4 Total all the notification appliance device loads and enter that number into line C 5 Make sure that the...

Страница 16: ...ubtotals mA mA Smoke Detectors Standby mA mA Alarm mA mA Standby mA mA Alarm mA mA Standby mA mA Alarm mA mA Standby mA mA Alarm mA mA Standby mA mA Alarm mA mA Standby mA mA Alarm mA mA B Current Sub...

Страница 17: ...quivalent material can be used to space the cabinet from the concrete surface and then attach the 5104B to that spacing surface Also mount any other desired components to the 1 4 spacing surface DO NO...

Страница 18: ...d electrician Figure 3 4 AC Transformer Connections 3 9 Battery Connection The battery provides backup power to the system during AC power loss Connect the 12 VDC battery SK Model 6712 as shown in Fig...

Страница 19: ...ected even after a single open or ground fault occurs When a single open or ground fault occurs the audible trouble signal will sound and the 5104 will report the trouble to the central station Figure...

Страница 20: ...tation Figure 3 7 shows how to wire a class B style B loop One side of each class B loop connects to a zone input ter minal and the other side of each loop connects to loop power For each loop use a 4...

Страница 21: ...e Detector Connection 4 wire smoke detectors must use a power supervision module Connect four wire smoke detectors as shown in Figure 3 8 Figure 3 8 4 wire Smoke Detector Connections Model 160150 Supe...

Страница 22: ...Non Supervised Notification Appliance Wiring Figure 3 9 illustrates how to wire a non supervised notification device to the control panel Figure 3 9 Non Supervised Alarm Bell Wiring Note Polarities sh...

Страница 23: ...w to wire a supervised notification device to the control panel Refer to Section 6 2 7 Step 14 to program the notification circuit s supervision properties Figure 3 10 Supervised Alarm Bell Wiring Not...

Страница 24: ...o the phone lines with a 7860 cable which plugs into an RJ31X phone jack The telephone company will install an RJ31X phone jack if you request them Both telephone lines must be installed to comply wit...

Страница 25: ...l box All wire runs must use 12 to 18 AWG wire with a maximum length of 1000 feet The annunciator must be supervised Follow these instruction to properly install the 5230 remote annunciator 1 Remove t...

Страница 26: ...and snapping the 5230 into place Note Refer to Section 5 for 5230 Operation ID Number Dip Switch 1 Dip Switch 2 Dip Switch 3 Dip Switch 4 0 On On On On 1 Off On On On 2 On Off On On 3 Off Off On On 1...

Страница 27: ...e 5104 as an add on communicator wire it as shown in Figure 4 1 Figure 4 1 5104 Add on Communicator Configuration Using 5104 Transformer for Power Note If power is supplied by the 5104 transformer the...

Страница 28: ...ion exist on the zone or zones indicated by Low AC AC power has been lost Trouble Line 1 Trouble condition on phone line 1 Trouble Line 2 Trouble condition on phone line 2 Dialer Trouble Indicates a d...

Страница 29: ...chpad Keystrokes and Their Task or Function Task or Function Keystroke Enter function or data Used initiate any command or to enter a step parameter into programming memory See examples below Enter Pr...

Страница 30: ...to a remote computer Installer Code Display Troubles Used to display any system troubles Installer or Operator Code Display Memory Used to display all system events including Alarms Troubles and Supe...

Страница 31: ...des 6 2 2 How to Enter and Exit Program Mode This section describes how to enter and exit programming mode 6 2 3 How to Enter Program Mode Follow these steps to enter program mode NOTICE TO USERS INST...

Страница 32: ...Figure 6 1 Example of 5230 Display To enter a new value into line 2 simple enter that value and press the enter key Yes or No Selections When the selection choices are Yes or No you can press any numb...

Страница 33: ...etting of those steps Table 6 2 Special Characters for Dialing Sequence Character Touchpad Inputs Displayed Character Pause A B C Look for second dial tone D Table 6 3 List of Programming Steps Step T...

Страница 34: ...the setting between Yes or No Step 10 Line 2 Prefix 1 to 8 digits None Enter 8 digits to phone line 2 Use special characters to add pauses and look for second dial tone characters into the line 2 pre...

Страница 35: ...d Trouble 1 Yes or No Yes Set priority for trouble reports Yes Priority phone number is 1 No Priority phone number is 2 Step 18 Send Test 1 Yes or No Yes Set priority for manual and auto test reports...

Страница 36: ...a sprinkler Supervisory when using SIA format No If you want troubles and alarms to report as fires Alarm Note Bells will only sound if No is select ed Step 24 Report Sprnk 6 Yes or No No Set how zon...

Страница 37: ...particular long distance carrier Use special characters to add pauses and look for second dial tone characters into the phone number See Table 6 2 for special characters Step 30 Phone 1 1 to 16 digit...

Страница 38: ...tion other than 0 3 will scroll through the available selections Step 40 Zone Response 2 1 See Step 39 Step 41 Zone Response 3 1 Step 42 Zone Response 4 1 Step 43 Zone Response 5 1 Step 44 Zone Respon...

Страница 39: ...ric digit to toggle the selection from Yes to No Yes If the 5104 is used as an add on communicator for a host panel This tells the 5104 not to test the battery or earth ground which could cause interf...

Страница 40: ...1400 Hz See Table 6 1 3 1 23 Old format transmits a 3 digit account number and a 1 digit alarm code Transmissions are acknowledged at 2300 Hz See Table 6 1 4 2 SK 4 2 Tone burst format transmits a 4 d...

Страница 41: ...rouble Code F1 F6 1 203 001 1 203 006 Sprinkler Trouble Restore 1 6 SJ1 SJ6 71 76 Restore Code E1 E6 3 203 001 3 203 006 Annunciator Trouble 1 3 ET1 ET3 33 Trouble Code FD 1 330 001 1 330 003 Annuncia...

Страница 42: ...store Code EB 3 351 000 Communications Failure Line 2 YC2 32 Trouble Code FC 1 352 000 Communications Restore Line 2 YK2 36 Restore Code EC 3 352 000 Manual Test RX0 30 Test Code EE 1 601 000 Automati...

Страница 43: ...uble condition on line 2 L5 On Dialer Trouble Indicates a dialer failed condition Earth Ground Fault Indicates that an earth ground fault condition exists Earth Pwr Fault Indicates that an earth power...

Страница 44: ...Flashes Trouble Com 2 Event reports auto test or manual test unable to report on line 2 Phone line voltage is O K but the panel was unable to communicate on line 2 Try dialing the phone number that y...

Страница 45: ...oard only Products that are returned in cabinets will be charged an additional 50 to cover the extra shipping and handling costs over board only returns Do not return batteries Silent Knight has the a...

Страница 46: ...S EITHER EXPRESSED OR IMPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY...

Страница 47: ......

Страница 48: ...Silent Knight 12 Clintonville Road Northford CT 06472 1610 203 484 7161 Fax 203 484 7118 www silentknight com...

Отзывы: