![SILENT KNIGHT 5104B Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/silent-knight/5104b/5104b_installation-and-operation-manual_1271092036.webp)
Model 5104B Installation Manual
151053-L8
6-6
Step 21
Report Sprnk #3
Yes or No
No
Set how zone 3 will report. Press any numeric-
digit to toggle the selection from Yes to No.
Yes = If you want to report troubles and alarms
as a sprinkler (Supervisory), when using SIA
format.
No = If you want troubles and alarms to report
as fires (Alarm).
Note:
Bells will only sound if “No” is select-
ed.
Step 22
Report Sprnk #4
Yes or No
No
Set how zone 4 will report. Press any numeric-
digit to toggle the selection from Yes to No.
Yes = If you want to report troubles and alarms
as a sprinkler (Supervisory), when using SIA
format.
No = If you want troubles and alarms to report
as fires (Alarm).
Note:
Bells will only sound if “No” is select-
ed.
Step 23
Report Sprnk #5
Yes or No
No
Set how zone 5 will report. Press any numeric-
digit to toggle the selection from Yes to No.
Yes = If you want to report troubles and alarms
as a sprinkler (Supervisory), when using SIA
format.
No = If you want troubles and alarms to report
as fires (Alarm).
Note:
Bells will only sound if “No” is select-
ed.
Step 24
Report Sprnk #6
Yes or No
No
Set how zone 6 will report. Press any numeric-
digit to toggle the selection from Yes to No.
Yes = If you want to report troubles and alarms
as a sprinkler (Supervisory), when using SIA
format.
No = If you want troubles and alarms to report
as fires (Alarm).
Note:
Bells will only sound if “No” is select-
ed.
Step 25
Latch Sprnk
Yes or No
No
Set how the sprinkler zone will operate. Press
any numeric-digit to toggle the selection from
Yes to No.
Yes = When the sprinkler zone shorts for a
duration longer than the Zone Response (set in
steps 39 through 44), the annunciator remains
active until reported or manually silenced.
No = When the sprinkler zone shorts for a
duration longer than the Zone Response (set in
steps 39 through 44), the zone will follow
system status and indicate a supervisory on
that zone for the duration of the faulted
condition.
Table 6-3: List of Programming Steps
Step #
Task
Choices
Default