SILENT ALERT SA3000 FIRE SAFE MANUAL 24/04/2015
Designed & Manufactured by Clofield Limited
Free technical helpline 01246 450789 www.silent-alert.co.uk
SignWave Unit
Part number:
SW3A-2208-EU
Dimensions:
H140mm x W50mm x D70mm (Excluding belt clip)
Weight:
278gms
Material:
Impact resistant fire retardant ABS
Power supply:
Integral NiMH 6Volt rechargeable battery pack.
Charger:
Intelligent boost, trickle and maintenance charging.
Fault conditions:
Low battery & radio failure.
Radio compliance:
In accordance with EN300 220-1.
Radio licence:
Licence exempt.
Range:
Up to 1000m in open air.
Other:
Integral field strength / data validation meter for system commissioning.
Preliminary radio coverage test
A preliminary radio coverage test is normally conducted prior to installation to ensure total
coverage throughout a building. It is recommended that a further radio coverage test is
performed prior to permanently securing the Fire Safe panel to a wall in case it needs to be
relocated. The Fire Safe panel should be mounted temporarily to a wall at between 1.5 and
1.75 meters from the ground away from large metal objects and lift shafts. For best results
locate the panel central to the building. In multi-storey buildings penetrations through steel
re-enforced concrete floors may be poor. In these situations coverage would be improved if
the panel is located one floor above ground level to provide coverage over three floors or
two levels above ground level to cover four floors. In-building coverage will vary from
building to building therefore it is essential that a full and thorough radio coverage test is
conducted. The range test procedure detailed later under the heading
Site Survey
should
be followed. If it is found that the coverage is inadequate then additional Fire Safe interfaces
may need to be added. In this case it will be necessary to change the signal patterns for
each panel to ensure there are no standing wave problems. This aspect is covered in more
detail under the heading
The use of more than one Fire Safe panel
below
.
Power Supply
It is necessary to supply the Interface Panel with a dedicated mains supply (220-240v AC 50
Hz) via its own un-switchable fused spur. The mains terminal block is located at the bottom left
hand side of the main PCB and is marked Earth (top) Neutral (middle) Live (bottom). The Panel
will also require a 6 Volt lead acid 4Ah back-up battery Type Y4-6 (Dimensions
H100mmxW47mmxD70mm).
It is necessary to connect the battery to the two wires with crimped connectors, before
connecting the mains to avoid a fault condition.