SILENT ALERT SA3000 FIRE SAFE MANUAL 24/04/2015
Designed & Manufactured by Clofield Limited
Free technical helpline 01246 450789 www.silent-alert.co.uk
Master Reset & Numeric Display Diagnostics
Master reset
The system will recover from a fault condition when the fault has been rectified. This however
can take a number of seconds. The master reset button can be used
to clear fault conditions
more quickly.
Numeric display diagnostics
The 4 digit LED display will display messages from the panel when an event occurs.
Fire alarm from the main panel
Panel is polling. Followed by flashing line to
indicate on board radio test.
Panel is disabled via the key on the right hand
side of the panel
Battery missing / low voltage. Replace the battery
with a new Y6-04. The panel will send a fault
condition to the fire alarm in this state.
Mains Failure. Check panel fuses and mains
supply is present. The panel will send a fault
condition to the fire alarm in this state.
Battery charging failure. Check that mains is present, the
condition of the battery leads and the battery itself. The panel
will send a fault condition to the fire alarm in this state.