MBA511
Datum 29.07.2015
Art. Nr. 81105
Änd. Stand 284/15
9
screening
screening
socket
pin
viewing side =
plug-in side
screen or metal housing must be provided.
The
running of wiring parallel to the mains supply
should be avoided.
• Contactor coils must be linked with spark sup-
pression.
Power supply:
24 VDC -20% ... +20%
Power consumption:
< 3 Watt
4.1 Connection type
(cable length ≤100 m)
12 pole plug pin:
Pin
Designation
A
SSI Data-
B
SSI Data+
C
SSI Cycle-
D
SSI Cycle+
E
+24 VDC
F
sinus
G
RS485 DÜA
H
RS485 DÜB
J
GND
K
N.C.
L
zero-setting entry
M
cosinus
4.2 Connector
12-pole mating connector straight
Available from
SIKO
as accessory art. no. 76572.
6. Open spacer (part 4) and put it over ferrules,
squeeze and push it onto part 3. Slot and keyway
of parts 3 and 4 must align.
7. Press parts 6 and 5 together; cut protruding
screening.
8. Push parts 2 and 7 together and screw
9. part 11 using appropriate tool.
10. Push part 8 into part 9 and slide both parts
into part 7.
11. Screw parts 10 and 7 together.
12. Push part 1 into part 2.
12-pole mating connector angle
Available from
SIKO
as accessory art. no. 79666.
1. Slip parts 6 to 10 over outer cable.
2. Strip cable.
3. Turn down screening.
4. Push part 5 onto ferrules.
5. Solder stranded wires at part 3 (follow connec-
tion diagram).
Please proceed as follows:
1. Mount seals (3x).
2. Stringing cable parts.
3. Dismantle cable and shield.
4. Thread-up wires through the housing.
5. Mount shielding ring and pinch ring.
6. Turn on the pressing screw very slightly.
7. Solder wires on insert.
8. Adjust the turnable shell inside the connector to
the required angular position (ensure position of
the stud) in steps of 90° (see chapter "Changing
the angle position").
9. Set in insert and distance sleeve.
10. Mount cover.
11. Fix pressing screw (approx. 10 ... 20 Nm).