AH36M
Commissioning English
AH36M · Date
05.03.2018 · Art.
No.
85966 · Mod.
status
1/18
18
PIN
Designation
1
Iout/Uout
2
+UB
3
GND
4
Set 2
5
Set 1
5 Commissioning
Function of alignment
The absolute encoder is adjusted by activating the corresponding set
inputs (Uin >12 V; Uin ≤ UB) (see chapter
4.2
).
The minimum range of measurement is 22.5°:
1. Turn shaft to the smallest position.
2. Activate input Set 1 (>1 sec.).
3. Turn shaft to the largest position.
4. Activate input Set 2 (>1 sec.).
The analog output is now adjusted to the new measuring range.
Resetting to factory settings
Activate both inputs Set 1 and Set 2 simultaneously for >1 sec. The factory
settings are then applied.
Representation Preset
Voltage output
Revolutions
viewing side = plug-in side