AG03/1
Installation English
AG03/1 · Date
30.05.2022 · Art.
No.
86426 · Mod.
status
116/22
39
`
Perform wiring work in accordance with the EMC measures IEC 61800-3
`
Check the correct execution of the EMC measures.
Danger of fire
Fuse protection is required as a protection against damage caused by
defective devices.
`
Electronic automatic fuses of the E-T-A company or load circle moni-
toring devices of the Murr Elektronik company are suitable solutions
for this purpose.
`
For the nominal currents refer to the technical data in chapter
.
Inrush, destruction of contacts
Operating voltage connUB (output stage) as well as +M/+UB
doesn’t have any starting current limiting. Starting current can be a multi-
ple of nominal current as a result of internal capacitance. When operating
voltage output stage is activated via switching of contacts, contacts can
be destroyed or fuse.
`
Use power pack which limits output current’s peak value to a value
acceptable for the contact.
`
Switch power input of the power pack rather than output voltage.
Electromagnetic compatibility (EMC)
The following measures are required in order to ensure electromagnetic
compatibility of the actuator:
`
Provide a separate power adapter for the supply of one or multiple
SIKO actuators.
`
All lines for connecting the actuator must be shielded.
`
The shield must be applied on both sides.
`
The retractable ferrite (supplied with the AG03/1) is to be attached to
the supply line near the 4-pole connector.
`
The drive is to earthed via the flat connection with a strand section of
at least 4 mm².
`
The maximum line length for IOL and IOL2 is 20 m.
Basically, all connections are protected against external interference.
Choose a place of operation that excludes inductive or capacitive interfer-
ence influences on the actuator. When mounting the system keep a maxi-
mum possible distance from lines loaded with interference. If necessary,
provide additional installations including screening shields or metallized
housings.
WARNING
WARNING
CAUTION
NOTICE