Operation
i
ndu
Q
®
- Series VMM
- 32 -
© SIKA
•
Ba_VMM_us
•
09/2018
Before changing the current settings, the
customer password has to be entered.
Otherwise, the settings only can be watched
but not changed.
The ESC key is used for discarding changes.
Volume flow QV unit:
Using this function, the physical unit, limit
values and the upper-range value of volume
flow can be defined.
For selecting the desired function please use
the key
or
. After choosing the
Volume
flow QV unit
function and pressing the
ENTER key, the following selection field will
be displayed.
Example:
For changing the parameter please refer to
the description in Section "Selection window
/ make a selection".
The following units are available:
Volume units:
m3 / s
m3 / min m3 / h
l / s
l / min
l / h
USG / s USG / min USG / h
UKG / s UKG / min UKG / h
ft3 / s
MGD
(Mega US Gallons /
day)
Mass units*:
kg / h
t / h
*
When selecting a mass unit the liquid density is
certainly required.
7.1.5.1
Scaling the outputs
The measuring variable volume flow rate is
shown by the VMM as well as an analog cur-
rent output as a pulse output.
The correlation of output and flow rate is not
fixed but it can be defined by the parameters
QV LRV
and
QV URV
(see Fig).
Volume flow lower-range value:
This function allows setting the lower-range
value for volume flow QV LRV which corre-
sponds to the lower-range value for the out-
put value.
For selecting the desired function please use
the key
or
. After choosing the function
Volume flow lower-range value
and
pressing Enter, the following selection field
will be displayed:
Example:
The unit for the QV LRV is defined by the
function
Volume flow unit
.
Usually the value for QV LRV is set to 0.0
(factory default).
Volume flow upper-range value:
This function is intended to set the upper-
range value for volume flow QV URV which
corresponds to the upper-range value for the
output value.
Volume flow QV
in [USG/min]
QV LRV = 0%
+0.000000 USG/min