Instruction Manual FireGuard 2
Mounting
20
13542E/5
4
Mounting
CAUTION!
Danger of the photometer falling onto the road if improperly mounted.
The following requirements must be met when fastening the instruments in place:
▪
When fastening the photometer, screws with a diameter of at least
M8
must be used.
▪
The material quality of the screws used must correspond to the local mounting and
installation guidelines.
4.1
General information on mounting the FireGuard 2
Figure 6: Installation position in the air flow
▪
The opening on the sampling point (X) must point in the direction of travel in the tunnel.
▪
The inclination of the photometer must not exceed 20°.
Installation of the measuring system is carried out in the following steps:
WORKSTEP
ADDITIONAL INFO / IMAGES
1.
Mount the photometer at the measuring posi-
tion.
▪
Installation with a variable mounting
bracket 0 .. 90° is made according to Sec-
tion 4.2.
▪
Installation in suspended ceilings is made
according to Section 4.3.
2.
Mount the SIPORT 2 connection box accord-
ing to Section 4.6.
3.
Carry out the electrical installation according
to Section 5.