Instruction Manual FireGuard 2
Electrical installation
34
13542E/5
5.8
Connecting the optional junction box
The photometer is connected to the junction box via a connector (1). There is the possibility
of connecting the junction box to the SICON-C (2) portable control unit. This enables opera-
tion directly on the photometer during servicing duties. Two cable glands (4) are available for
connecting to the control system.
Figure 16: Junction box when open
Instrument socket for connecting
the photometer
Instrument socket for connecting the
SICON-C
Terminal strip (cable cross-section:
0.08 .. 1.5 mm
2
)
Two cable glands, clamping range
8 .. 13 mm
Establish the electrical connections in the junction box as follows:
TERMINAL
DESIGNATION
CABLE COLOR
(SIGRIST) 8 WIRES
WITH SIPORT 2
CABLE COLOR
(SIGRIST) 4 WIRES
WITH SICON
REMARKS
GND
Black
Blue
Are connected to
each other
GND
White
−
24V
Green
Red
Are connected to
each other
24V
Brown
−
E, ground /
−
Cable shielding
E, ground /
−
−
SA
Blue
Gray
SB
Red
Yellow
A
Gray
−
B
Yellow
−