background image

-2-

Series MHE-BB

02.19.00

Moonlite LED

 High Output Emergency Light

With Battery Backup

Fig 2

4 9/16"

ADJUSTABLE FOR PANELS

1/4" - 1" THICK

CEILING

GROUND

ALTERNATE CABLE ENTRY

POWER ASSBY
NUTS (2) #8-32

120/277 VAC
INPUT

AC CONNECTOR

LAMP PLUG 3-PIN

POWER ASSEMBLY

LAMP ASSEMBLY

PTT PLUG 8-PIN

G

L

N

BATTERY PLUG

2-PIN

BATTERY 

2. See Fig 2. Position Back Box assembly so that edge of box is flush or just below finished ceiling 
surface.  NOTE: Fixture weight is 13 lb.  Install drop wires when fixture is mounted on T-Bar grids in 
drop ceilings. 

3. Route AC supply wiring into back box through KO's on top or sides of housing as shown.  Connect 
GROUND wire to #8 stud inside housing then trim BLACK and WHITE input/output wires to approx. 8” 
inside housing. 

4. Remove male half of AC lamp connector from BLACK/WHITE leads on power supply assembly. 
Strip AC input supply wires and push-connect BLACK (LINE) and WHITE (NEUTRAL) IN-OUT wires 
into lamp connector.     

Содержание Moonlite LED MHE-BB Series

Страница 1: ...erformed by qualified personnel 4 Consult your local building code for approved wiring and installation 5 Do not use outdoors 6 Do not use this equipment for other than intended use 7 Do not let power cords touch hot surfaces 8 Mount and secure the fixture at a location and height to avoid ready access and tampering by unauthorized persons 9 The use of accessory equipment is not recommended by the...

Страница 2: ...hat edge of box is flush or just below finished ceiling surface NOTE Fixture weight is 13 lb Install drop wires when fixture is mounted on T Bar grids in drop ceilings 3 Route AC supply wiring into back box through KO s on top or sides of housing as shown Connect GROUND wire to 8 stud inside housing then trim BLACK and WHITE input output wires to approx 8 inside housing 4 Remove male half of AC lamp ...

Страница 3: ...ORE CONNECTING BATT PLUG CONFIRM AC SUPPLY IS ON IF NOT ON HIGH OUTPUT LAMP WILL LIGHT When AC supply is ON connect BATTERY PLUG 4 Remove Hanging Wire and place Lamp Assembly into position Confirm that PTT and LAMP wiring plugs remain clear of Lamp Assembly in cavity above circuit Board Insert 2 Trim Plate screws and tighten 5 Push BATTERY PLUG into cavity at side of battery 6 5 With AC power ON an...

Страница 4: ...in recess If not using J Box install 2 Screw Anchors for 10 mount screws supplied at 11 between centers If using J Box install at 9 1 2 between centers 2 Proceed as for Surface Mount from Step 3 to END Fig 3 Surface Mount 220 VFWAvenue Grasonville MD21638 TEL 410 827 8300 Fax 410 827 8866 sales signtexinc com www signtexinc com Signtex Inc LIGHTING OPTIONAL J BOX SCREW ANCHORS 120 277 VAC INPUT G ...

Отзывы: