-2-
Series MHE-BB
02.19.00
Moonlite LED
™
High Output Emergency Light
With Battery Backup
Fig 2
4 9/16"
ADJUSTABLE FOR PANELS
1/4" - 1" THICK
CEILING
GROUND
ALTERNATE CABLE ENTRY
POWER ASSBY
NUTS (2) #8-32
120/277 VAC
INPUT
AC CONNECTOR
LAMP PLUG 3-PIN
POWER ASSEMBLY
LAMP ASSEMBLY
PTT PLUG 8-PIN
G
L
N
BATTERY PLUG
2-PIN
BATTERY
2. See Fig 2. Position Back Box assembly so that edge of box is flush or just below finished ceiling
surface. NOTE: Fixture weight is 13 lb. Install drop wires when fixture is mounted on T-Bar grids in
drop ceilings.
3. Route AC supply wiring into back box through KO's on top or sides of housing as shown. Connect
GROUND wire to #8 stud inside housing then trim BLACK and WHITE input/output wires to approx. 8”
inside housing.
4. Remove male half of AC lamp connector from BLACK/WHITE leads on power supply assembly.
Strip AC input supply wires and push-connect BLACK (LINE) and WHITE (NEUTRAL) IN-OUT wires
into lamp connector.