background image

 

 

 

   

Page  6  of 12  DocNo.DCP0001326  DSM  05/01/05  rev7

 

 

The P2.200LS is designed to operate with two 12 Volt VRLA batteries connected in series. 

BS5839-8  1988  requires  that  batteries  must  be  capable  of  operating  the  system  according  to  the  project 
requirements (normally 24 Hours in a quiescent current state plus 30 minutes in full alarm). It also requires 
that batteries be sized so as to provide 25% overcapacity to allow for loss of capacity over time. 

It is also necessary to allow for the current drawn by any ancillary equipment connected to the Auxiliary power 
output. Auxiliary devices should be connected to different P2.200LS amplifiers in order to spread the load as 
evenly as is practical. 

Quiescent Battery capacity 

The current drawn in the quiescent state is 75 mA per amplifier module, 150 mA total. 

The current drawn in the quiescent state with all fault indicators lit is 150 mA per module, 300 mA total. 

Therefore, for worst case, the power drawn over 24 Hours is 7.2 AHr. 

Alarm Condition Battery Capacity 

It is difficult to predict the exact current drawn in alarm condition so the following approximation is used. 

Emergency messages consist of a tone, silence, message and silence. 

The average power content of speech is approximately 5%. 

The average power content of a tone is approximately 20% 

The average power content of silence is nil. 

A conservative estimate of current draw is therefore 10% of the peak. 

The peak current drawn from each amplifier channel is 11 Amps, 22 Amps total. 

10% of the peak value is therefore 2.2 Amps or, for 30 minutes, 1.1 AHr. 

However, batteries must be de-rated by 50% at high discharge rates and so a figure of 2.2 AHr is taken 

If 60 minutes in alarm is required, 4.4 AHr will be required. 

Total Battery Capacity 

Add alarm state battery capacity to the quiescent capacity and the capacity required is 9.4 AHr 

Add 1/3 to allow for a 25% loss of capacity over time and the smallest battery that can be used is 12.5 AHr. 

The smallest standard battery above this size is 18 AHr and 27 AHr gives even more spare capacity. 

Additional battery capacity for ancillary equipment 

Add the capacity required for any ancillary equipment, plus one third for battery aging. These figures do not 
change in an alarm condition. 

Worst case quiescent current drawn at 24V d.c.  

SS2N 

= 75 mA 

= 1.84 AHr + 1/3  

= 2.44 AHr 

Psiren 

= 50 mA 

= 1.23 AHr + 1/3  

= 1.63 AHr 

FCB 

= 50 mA 

= 1.23 AHr + 1/3  

= 1.63AHr 

Integrity Mainframe 

= 300 mA 

= 7.35 AHr + 1/3  

= 9.78 AHr 

MP2 

=   50 mA 

= 1.23 AHr + 1/3  

= 1.60 AHr 

MPP panel (any) 

= 150 mA  (all LEDs lit) 

= 3.68 AHr + 1/3  

= 4.89 AHr 

Batteries  must  be  connected  via  a  suitable  fuse.  We  recommend  DIN  mounted  cartridge  fuse  holders  ref 
RS371-0340 and 20A RS230-3496 cartridge fuses. 

Correct Power-up Sequence 

Plug in mains connector 

Make sure external battery fuse is out of circuit 

Connect battery connector to amplifier 

Switch on mains 

Connect battery fuse 

Power-related fault indicators should extinguish 

If the batteries are connected before the mains supply is turned on the inrush current will weaken the internal 
battery fuse.

DC power operation and Battery Calculation

 

Содержание Pulse 2.200 LS

Страница 1: ...d in series to give 400W at 100V line The power supply has a 24 Vd c battery input and an onboard battery charger Technical Description Amplifier Modules The Aux and Main line level inputs are de balanced and pass via level controllers and an analogue switch into a summing amplifier where they are mixed If the contact input is asserted 470 ohms to ground a logic circuit disconnects the aux input T...

Страница 2: ... AUTOMOTIVE BLADE TYPE EXCEPT MAINS INLET FUSE AMP A FAULT AMP B FAULT OK SIP4 PSU FAULT SIP3 AMP B FAULT SIP2 AMP A FAULT SIP1 SLEEP LINE IN AUX 0dB LEVEL P2 200LS AMPLIFIER MODULE BLOCK DIAGRAM TWO PER P2 200LS ISSUE 1 LINE IN MAIN 0dB LEVEL MONITOR ANALOGUE SWITCH ANALOGUE SWITCH CONTROL 50 V 100V 0V CONTACT PTT IN OPEN CIRCUIT FAULT SHORT CIRCUIT FAULT DETECT FAULT HSP2 LOAD HIGH FAULT HSP1 LO...

Страница 3: ...sed as it does not comply with BS5839 8 5 Load Hi The load monitoring system has detected an open circuit or higher impedance than was set at commissioning 6 Load Low The load monitoring system has detected a closed circuit or lower impedance than was set at commissioning 7 Contact Fault The main input control contact or wiring is either open circuit or short circuit 8 Tone fail Load Hi and Load L...

Страница 4: ...6 Aux audio input 11 LEDs OC The main input control wiring is open circuit SC The main input control wiring is short circuit E Earth fault The 100V loudspeaker line has a short to ground Hi Load High Open circuit detected or a impedance higher than commissioned TF Tone Fail The monitor tone on the input signal is not detected Lo Load Low Closed circuit detected or lower impedance than commissioned...

Страница 5: ...dust levels 5 susceptible to vibration Caution To prevent electric shock do not remove the cover AC power operation Due to the size and inductance of the power transformer depending on where in the cycle the power is switched on the inrush current that is drawn when this device is connected can be as much as 150 Amps It is therefore essential that mains power is only derived from an automatic soft...

Страница 6: ...awn from each amplifier channel is 11 Amps 22 Amps total 10 of the peak value is therefore 2 2 Amps or for 30 minutes 1 1 AHr However batteries must be de rated by 50 at high discharge rates and so a figure of 2 2 AHr is taken If 60 minutes in alarm is required 4 4 AHr will be required Total Battery Capacity Add alarm state battery capacity to the quiescent capacity and the capacity required is 9 ...

Страница 7: ...oudspeaker line continuity be monitored not the loudspeakers themselves Loudspeaker Spurs Note that this implies that spurs are not allowed If a loudspeaker output is to be split to drive two circuits this is only possible using the SPLIT100 Line Splitter which protects either circuit against a short circuit in the other circuit The SPLIT100 is provided with one EOL device so that one EOL can be u...

Страница 8: ...a 22Khz monitoring tone This will be shown by a sticker on the unit iX LS units without a sticker must be replaced with 22Khz units Older iX LS units use a 20 Khz monitoring tone End of line units supplied with the amplifier must also be fitted Connecting the P2 200 to a SigNET SS2n Network station including battery backup 1 SS2n feeding both amplifier modules 2 SS2n feeding only one amplifier mod...

Страница 9: ...lead from a SigNET routing matrix is connected to both Main Inputs a 2 Check that the monitoring tone is not disabled the tone fail TF indicator is not lit 3 No audio should be routed into the Main input except for the 22 kHz monitoring tone 4 Using an oscilloscope e g Maplin Part No IN02158 or true r m s voltmeter RS218 0265 capable of reading up to 25 kHz connect to each 100V line output across ...

Страница 10: ...led default Battery monitoring enabled Disabled Battery monitoring disabled this removes the battery fault from the front panel if batteries are not fitted Sleep Mode Disabled default This facility is not used as it does not comply with BS5839 8 All other jumpers on the unit are all for SigNET s internal use test purposes only SIP port These four fault outputs pass via a 16 pin dual in line socket...

Страница 11: ...ting area 75mA 150mA with fault lights lit and full load monitoring 11A Physical Material Colour Width Height Depth Weight 18swg Zintec sheet steel Black RAL 9500 semi gloss 430mm 88mm 315mm behind front panel 17kg Power supply charger AC input DC input Charging voltage Charging current Monitoring Aux Supply SIP Port 230 VAC 20 22 to 34 V DC 27 6 V DC 3A Short circuit and battery high impedance 1A...

Страница 12: ...se locations Fuses are commonly available automotive blade types SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE SigNET AC Limited 6 Tower Road Glover Estate Washington Tyne Wear NE37 2SH Tel 44 0 191 417 4551 Fax 44 0 191 417 0634 info signet ac com www signet ac com ...

Отзывы: