background image

page 7 of 8

‡ SIGNET

 8550-1 Flow Transmitter

Adjust the LCD contrast for best viewing.  A setting of 1 is lower contrast, 5 is higher.
Select lower contrast if the display is in warmer ambient surroundings.

Set the decimal to the best resolution for your application.  The display will automatically
scale up to this restriction.
Select *****., ****.*, ***.**, **.***   or *.****

Set the totalizer decimal to the best resolution for your application.
Select ********., *******.*, or ******.**

.OFF provides the quickest output response to changes in flow.
LOW averaging  = 4 seconds, HIGH averaging = 8 seconds of input signal.
Longer averaging produces more stable display and output response.

Lock Off : No key code required to reset the resettable totalizer.
Lock On : The Key Code must be entered to reset the resettable totalizer.

Adjust the minimum and maximum current output. The display value represents the
precise current output.
Adjustment limits:
•  3.80 mA < 4.00 mA > 5.00 mA
•  19.00 mA < 20.00 mA > 21.00 mA
Use this setting to match the system output to any external device.

Active HIGH: This setting is used to turn a device (pump, valve) ON at the setpoint.
Active LOW:  This setting is used to turn a device OFF at the setpoint.

Press UP or DOWN keys to manually order any output current value from 3.6 mA to
21.00 mA to test current loop output.

Press UP or DOWN keys to manually toggle the  state of open collector output.

Contrast:

3

>

Flow Decimal

*****.

>

Total Decimal

******.**

>

Averaging:

Off

>

Total Reset:

Lock Off

>

Loop Adjust:

          4.00      mA >

Loop Adjust:

          20.00     mA >

Output Active:

Low

>

Test Loop:

>

Test Output:

>

Options Menu

Display

(Factory settings shown)

Description

Содержание 8550-1

Страница 1: ...rrent output 4 to 20 mA isolated fully adjustable and reversible Flow Flow 6 25 GPM Total 1234567 8 ENTER 3 8550 090 1 1 Installation ProcessPro transmitters are available in two styles panel mount and field mount The panel mount is supplied with the necessary hardware to install the transmitter This manual includes complete panel mounting instructions Field mounting requires one of two separate m...

Страница 2: ...ection Wiring Removal Procedure 1 Press the orange terminal lever downward with a small screwdriver to open terminal jaws 2 When fully open remove wire from terminal 2 1 Terminals 5 and 6 Open collector Output A transistor output programmable see CALIBRATE menu as High or Low setpoint with adjustable hysteresis Volumetric pulse Frequency based on flow rate May be disabled Off if not used Terminals...

Страница 3: ...Loop Input 4 20 mA Loop Input 4 20 mA Internal PLC Connection Connection to a PLC Recorder separate supply PLC or Recorder Loop Input 4 20 mA in Loop Input 4 20 mA in DC 12 24 V Power Supply Power Supply Example Two transmitters connected to PLC Recorder with separate power supply Transmitter 2 4 3 2 1 DC 12 24 V Power Supply Power Supply Transmitter 1 4 3 2 1 Transmitter Terminals 4 3 2 1 Sys Pwr...

Страница 4: ...lse that is relative to the flow volume or to the flow rate Low Output triggers when the flow rate is less than the setpoint The output will relax when the flow rate moves above the setpoint plus the hysteresis value High Output triggers when the flow rate is greater than the setpoint The output will relax when the flow rate drops below the setpoint plus the hysteresis value Frequency Output is a ...

Страница 5: ... UP UP DOWN keys in sequence After entering the Key Code the display will show the first item in the selected menu Step 3 Scroll menu with UP or DOWN arrow keys Step 4 Press RIGHT ARROW key to select menu item to be edited The first display element will begin flashing Step 5 Press UP or DOWN keys to edit the flashing element RIGHT ARROW key advances the flashing element Step 6 Press ENTER key to s...

Страница 6: ...sired mode of operation for the Open Collector output Options available are High Low volumetric Pulse or Frequency The signal may be disabled Off if not used In Low or High Mode the Open Collector output will be activated when the Flow rate reaches this value Be sure to modify this setting if you change the Flow Units The Open Collector output will be deactivated at Setpoint Hysteresis depending o...

Страница 7: ...zer Lock On The Key Code must be entered to reset the resettable totalizer Adjust the minimum and maximum current output The display value represents the precise current output Adjustment limits 3 80 mA 4 00 mA 5 00 mA 19 00 mA 20 00 mA 21 00 mA Use this setting to match the system output to any external device Active HIGH This setting is used to turn a device pump valve ON at the setpoint Active ...

Страница 8: ...e place to the right Increase Pulse volume setting Decrease pulse width setting Reduce system flow rate Enter K factor from 0 0001 to 99999 Change the hysteresis value Replace transmitter SIGNET Signet Scientific Company 3401 Aerojet Avenue El Monte CA 91731 2882 U S A Tel 626 571 2770 Fax 626 573 2057 For Worldwide Sales and Service visit our website gfsignet com Or call in the U S 800 854 4090 G...

Отзывы: