BA_EE220_e // v3.2 // Technical data subject to change // 193532

Operating Instructions

EE220

Humidity / Temperature  

Transmitter

Содержание EE220

Страница 1: ...BA_EE220_e v3 2 Technical data subject to change 193532 Operating Instructions EE220 Humidity Temperature Transmitter...

Страница 2: ...of the products described This publication might contain technical inaccuracies or typographical errors The content is revised regularly and is not subject to change management The manufacturer reserv...

Страница 3: ...Probe protection 7 5 2 2 Probe removal 7 6 Electrical Connections 7 6 1 Connection Diagram 8 7 User Interface 8 7 1 Display 8 8 RH and T Adjustment of the EE07 Probes 9 8 1 Definitions 9 8 2 EE07 adj...

Страница 4: ...ioning shall be performed by qualified personnel only 1 2 2 Mounting start up and operation The humidity temperature transmitter has been produced under state of the art manufacturing conditions has b...

Страница 5: ...available in plastic or in stainless steel enclosure and can be plugged onto the basic unit either directly or with M12 extension cables up to 10 m 32 8 ft long An optional kit facilitates the mountin...

Страница 6: ...5 31 90 3 54 90 3 5 4 116 4 57 50 8 2 135 5 31 Fig 1 Mounting of metal and polycarbonate housing 4 2 Connecting the EE07 sensing probes The humidity RH probe or the combined humidity and temperature R...

Страница 7: ...e plastic protection cap HA010783 on the probe before starting cleaning or sterilizing and remove it after that This is not necessary for the EE 07MT metal temperature probe 5 2 2 Probe removal When r...

Страница 8: ...T Calib RH Calib 0 1V 0 5V 0 10V Calib T RH selection of output 2 DISPLAY socket for optional display 3 CALIB LED continuously on indicates adjustment mode 1 flash confirms reset to factory calibratio...

Страница 9: ...ently it is possible to replace the probes at any moment Start the adjustment procedure with the low point e g 30 RH and continue with the high point e g 80 RH For accurate calibration or adjustment t...

Страница 10: ...iddle of the RH and T measurement range of main interest 1 Set the jumper to RH calib or to T Calib 2 Place the probe into the corresponding calibrator and let it stabilize at the selected RH or T val...

Страница 11: ...www epluse com and the EE PCS Product Configuration Software free download at www epluse com configurator 9 Functional and Accuracy Check of EE220 Basic Unit The EE220 basic unit can be checked with...

Страница 12: ...connected as in Fig 5 power supply for 0 1 V 10 35 V DC 9 29 V AC for 0 10 V 15 35 V DC 15 29 V AC power supply 20 35 V DC RL 500 11 35 V DC RL 50 EE220 x1x x3x Fig 5 Voltage output For the EE220 wit...

Страница 13: ...ramount importance to assure best thermal contact between EE03 and the surface to monitor EE03 can be adjusted neither together with the EE220 basic unit nor individually With EE03 connected the S1 an...

Страница 14: ...front cover and fix it with the four screws 13 Spare Parts and Accessories See also data sheet Accessories Description Order Code Display and metal front cover D07M Display and polycarbonate front cov...

Страница 15: ...ut 10 35 V DC Load resistor for 4 20 mA output RL Uv 10V 0 02 A Current consumption typ 10 mA for DC supply typ 20 mAeff for AC supply Electrical connection screw terminals max 2 5 mm2 Cable gland M16...

Страница 16: ...cn BEIJING Tel 86 10 84992361 info epluse cn SHANGHAI Tel 86 21 61176129 info epluse cn E E GERMANY www epluse de Tel 49 6172 13881 0 info epluse de E E FRANCE www epluse fr Tel 33 4 7472 35 82 info...