SignalFire Telemetry 

 

7

 

Point-to-Point Mode 

In Point-to-Point mode, a WIOM Mini that is set to Gateway mode will mirror its digital 
inputs to the outputs of a Module set to Node, and vice-versa.  Point-to-Point mode is 
only valid for a pair of WIOM Mini modules. For example, if Digital Input 1 on the Gateway 
is shorted to GND (logic 1), Digital Output 1 on the Node is energized, and vice versa. 
Because the WIOM Mini A does not have an analog output, the analog input is not used.

 

 

 

Point-to-Point Mode. Inputs from one module are mirrored as outputs on the other 

When set to Point-to-Point mode, the WIOM Minis will not be viewable through a SignalFire Gateway 
as they will be on their own network. The module that is set to Gateway will be locked to Slave ID 1.

 

 

WIOM-Mini to WIOM Mode 

A WIOM Mini and a regular WIOM can also operate in Point-to-Point mode with each other. In this 
configuration the WIOM will mirror the WIOM Mini A’s analog input to its analog output 1. The DI’s 
will be mirrored in both directions. The WIOM must be configured in Gateway mode while the WIOM-
mini must be in node mode. 

 

 

 

 

Содержание Wireless I/O Module Mini

Страница 1: ...tal I O to a SignalFire Gateway or mirror the digital I O wirelessly another Wireless I O Mini Module acting as a wire replacement The SignalFire Wireless I O Module Mini has the following features 1 Analog input 1 5V 2 Digital inputs 2 Relay outputs 2 SPDT Wide range DC power input 6 36 VDC Low power consumption DIN rail mount with pluggable screw terminal blocks Status LEDs ...

Страница 2: ... Analog Input 0 5V Signal 10V Max Digital Inputs Dry Contact or 30 Volts Max push pull 2kHz maximum frequency Digital Outputs 2 SPDT s max 30 VDC 2 Amps 250 VAC 0 25 Amps Radio Frequency Compliance 902 928MHz ISM Band FHSS radio RP SMA connector FCC and IC Certified Contains FCC ID W8V SFTS500 IC 8373A SFTS500 Certified for use in Class I Division 2 Groups A B C D Temperature Code T5 ...

Страница 3: ...ISSEMENT RISQUE D EXPLOSION La substitution de composants peut rendre ce materiel inacceptable pour les emplacements de classe I division 2 WARNING EXPLOSION HAZARD Do not disconnect while circuit is live unless area is known to be nonhazardous AVERTISSEMENT RISQUE D EXPLOSION Ne débranchez pas lorsque le circuit est en direct sauf si la zone est connue pour être nonhazardous WARNING The Wireless ...

Страница 4: ...input terminal to ground to convert the signal to 1 5V 1 5V Signal GND 4 20mA Signal GND A Input 1 A Input 1 Digital Inputs The digital inputs 2 total can be dry contact or voltage must be push pull and pull to ground 30 Volts max Be sure to connect the ground bus from the module to either the ground of the voltage device or the dry contact The digital inputs report their current state as well as ...

Страница 5: ...tatus LED also indicates the signal strength between it and its module pair In addition there are TX RX LEDs to indicate radio messages to from the module The status LED will blink once a second if it is not connected to another module If the node is connected to its paired module it will blink a link quality code every 3 seconds 3 Blinks Strong Signal 2 Blinks Good Signal 1 Blink Weak Signal Each...

Страница 6: ...ll WIOM Minis on the network must be set to Node and they will communicate with a SignalFire Gateway For Point to Point set one WIOM Mini to Gateway and one WIOM Mini to Node on a network that has no other devices Node Mode In Node mode the WIOM Mini will send its analog and digital inputs outputs to the Gateway All IO and then be read set from a PLC via Modbus Node Mode The Gateway reads all inpu...

Страница 7: ...put the analog input is not used Point to Point Mode Inputs from one module are mirrored as outputs on the other When set to Point to Point mode the WIOM Minis will not be viewable through a SignalFire Gateway as they will be on their own network The module that is set to Gateway will be locked to Slave ID 1 WIOM Mini to WIOM Mode A WIOM Mini and a regular WIOM can also operate in Point to Point m...

Страница 8: ...ave the same Radio Network Radio Network Group and Corporate ID Encryption Key as the Gateway For two Wireless I O Module Minis to communicate in Point to Point mode they must share the same Radio Network Radio Network Group and Corporate ID Encryption but not share those settings with any other SignalFire network To use an Encryption Key in lieu of a Corporate ID check off the Enable Encryption b...

Страница 9: ...ire Gateway If used this timeout must be set higher than the Modbus coil write frequency of the Modbus master device This option is available for both Point to Point and Node mode Analog Scaling Node Mode only Analog scaling can be used to scale an analog input to engineering units For example for a 0 1000psi sensor set the scale low to 0 and scale high to 1000 The scaled value will now be display...

Страница 10: ...04 41105 Relay 2 State 03 04 Read Only 1105 41106 AI1 Scaled Reading Float High Word 03 04 Read Only 1106 41107 AI1 Scaled Reading Float Low Word 03 04 Read Only 1107 41108 DI1 Total Counts Unsigned int High Word 03 04 Read Only 1108 41109 DI1 Total Counts Unsigned int Low Word 03 04 Read Only 1109 41110 DI2 Total Counts Unsigned int High Word 03 04 Read Only 1110 41111 DI2 Total Counts Unsigned i...