background image

 

Rev 1.5 

SignalFire Telemetry 

 

4

 

 

Connections and Components

 

 

Power 

Power must be provided by the Power Input screw terminals (6-36VDC). The module 
power requirements at 12VDC is 25mA average plus 15mA per energized relay channel.

 

 

Antenna 

The antenna port is standard RP-SMA connector. Connect this port to a suitable 900MHz antenna.  
SignalFire can supply a variety of antennas for use with the modules. 

 

 

Analog Input 

The analog input operates as a passive voltage input (1-5V).

 

Wire the analog voltage to the set of screw terminals. Maximum input voltage is 10 Volts. If the input 
is a 4-20mA signal, use a high-precision 250Ω resistor from the analog input terminal to ground to 
convert the signal to 1-5V.

 

 

   

 

 

1-5V Signal

GND

4-20mA Signal

GND

A. Input 1

A. Input 1

 

 

Digital Inputs 

The digital inputs (2 total) can be dry contact or voltage (must be push-pull and pull to ground, 30 
Volts max). Be sure to connect the ground bus from the module to either the ground of the voltage 
device or the dry contact.

 

 

The digital inputs report their current state, as well as input frequency. The DI pulse counter 
increments only when the state changes from 0 to 1. The Instantaneous Frequency registers are the 
number of pulses per second within 2 seconds of check-in multiplied by 10. The Average Frequency 
registers are the number of pulses per second over the period between two check-ins multiplied by 
10. The Counts/Min registers are the total number of pulses per minute between two check-ins 
multiplied by 10.

 

 
 

Содержание Wireless I/O Module Mini

Страница 1: ...tal I O to a SignalFire Gateway or mirror the digital I O wirelessly another Wireless I O Mini Module acting as a wire replacement The SignalFire Wireless I O Module Mini has the following features 1 Analog input 1 5V 2 Digital inputs 2 Relay outputs 2 SPDT Wide range DC power input 6 36 VDC Low power consumption DIN rail mount with pluggable screw terminal blocks Status LEDs ...

Страница 2: ... Analog Input 0 5V Signal 10V Max Digital Inputs Dry Contact or 30 Volts Max push pull 2kHz maximum frequency Digital Outputs 2 SPDT s max 30 VDC 2 Amps 250 VAC 0 25 Amps Radio Frequency Compliance 902 928MHz ISM Band FHSS radio RP SMA connector FCC and IC Certified Contains FCC ID W8V SFTS500 IC 8373A SFTS500 Certified for use in Class I Division 2 Groups A B C D Temperature Code T5 ...

Страница 3: ...ISSEMENT RISQUE D EXPLOSION La substitution de composants peut rendre ce materiel inacceptable pour les emplacements de classe I division 2 WARNING EXPLOSION HAZARD Do not disconnect while circuit is live unless area is known to be nonhazardous AVERTISSEMENT RISQUE D EXPLOSION Ne débranchez pas lorsque le circuit est en direct sauf si la zone est connue pour être nonhazardous WARNING The Wireless ...

Страница 4: ...input terminal to ground to convert the signal to 1 5V 1 5V Signal GND 4 20mA Signal GND A Input 1 A Input 1 Digital Inputs The digital inputs 2 total can be dry contact or voltage must be push pull and pull to ground 30 Volts max Be sure to connect the ground bus from the module to either the ground of the voltage device or the dry contact The digital inputs report their current state as well as ...

Страница 5: ...tatus LED also indicates the signal strength between it and its module pair In addition there are TX RX LEDs to indicate radio messages to from the module The status LED will blink once a second if it is not connected to another module If the node is connected to its paired module it will blink a link quality code every 3 seconds 3 Blinks Strong Signal 2 Blinks Good Signal 1 Blink Weak Signal Each...

Страница 6: ...ll WIOM Minis on the network must be set to Node and they will communicate with a SignalFire Gateway For Point to Point set one WIOM Mini to Gateway and one WIOM Mini to Node on a network that has no other devices Node Mode In Node mode the WIOM Mini will send its analog and digital inputs outputs to the Gateway All IO and then be read set from a PLC via Modbus Node Mode The Gateway reads all inpu...

Страница 7: ...put the analog input is not used Point to Point Mode Inputs from one module are mirrored as outputs on the other When set to Point to Point mode the WIOM Minis will not be viewable through a SignalFire Gateway as they will be on their own network The module that is set to Gateway will be locked to Slave ID 1 WIOM Mini to WIOM Mode A WIOM Mini and a regular WIOM can also operate in Point to Point m...

Страница 8: ...ave the same Radio Network Radio Network Group and Corporate ID Encryption Key as the Gateway For two Wireless I O Module Minis to communicate in Point to Point mode they must share the same Radio Network Radio Network Group and Corporate ID Encryption but not share those settings with any other SignalFire network To use an Encryption Key in lieu of a Corporate ID check off the Enable Encryption b...

Страница 9: ...ire Gateway If used this timeout must be set higher than the Modbus coil write frequency of the Modbus master device This option is available for both Point to Point and Node mode Analog Scaling Node Mode only Analog scaling can be used to scale an analog input to engineering units For example for a 0 1000psi sensor set the scale low to 0 and scale high to 1000 The scaled value will now be display...

Страница 10: ...04 41105 Relay 2 State 03 04 Read Only 1105 41106 AI1 Scaled Reading Float High Word 03 04 Read Only 1106 41107 AI1 Scaled Reading Float Low Word 03 04 Read Only 1107 41108 DI1 Total Counts Unsigned int High Word 03 04 Read Only 1108 41109 DI1 Total Counts Unsigned int Low Word 03 04 Read Only 1109 41110 DI2 Total Counts Unsigned int High Word 03 04 Read Only 1110 41111 DI2 Total Counts Unsigned i...

Отзывы: