S-DIAS SAFETY SNC INCREMENTAL ENCODER 

SNC 021 

 

02.12.2019 

 

Page 29 

12  Important Notes for Two-channel Application 

When  using  the  SNC  021  module  in  compliance  with 

SIL  3

  or 

SIL  CL  3

  according  to  EN 

62061 and 

PL e

Cat. 4

 according to EN ISO 13849-1, it must be taken into consideration 

that for 2-channel application,  a part  of the  possible  wiring errors  can  only  be  detected  by 
comparing the measurement results of both encoders in the Safety application of the Safe 
CPU. The inversion of signal lines A+ with A- as well as B+ with B- are one of these errors. 
Mechanical  errors,  such  as  a  detached  coupling  can  also  be  detected  only  in  the  Safety 
application of the Safe CPU. 
 
To  meet  the  requirements  of  the  diagnostic  coverage  ratio,  both  encoders  must  be 
synchronously monitored in the Safety application of the Safe CPU. 
 
For  synchronous  monitoring,  the  functional  Safety  block  SF_SkewMonitor  (see  chapter 
“Numerical Function Blocks” in the SafetyDesigner tool help) must be placed in the Safety 
project and used according to the documentation. 
 
The  inputs  S_ChnValue1 and  S_ChnValue2 of  the  functional  Safety  blocks must  be  wired 
with  the  input  information  _Chn1Value  and  S_Chn2Value  (synchronous  monitoring  of  the 
position) or alternatively, with S_Chn1Speed and S_Chn2Speed (synchronous monitoring of 
the speed) of the SNC 021 module. 
 
The required tolerance must be defined by the user. During synchronous monitoring via the 
position, it must be taken into consideration that if there is the possibility of a position overflow, 
the scaling parameter can cause position jumps. In such a case, the scaling parameter for 
calculating  the  position  should  be  left  at  the  default  settings  (factor  and  divisor 
are 1), or synchronous monitoring performed using the speed. 
 

If the system is not in Safe mode, synchronous monitoring must be performed 

according to the previously mentioned criteria 

 

Si le système n'est pas en mode Safe, une surveillance synchrone doit être effectuée 

selon les critères mentionnés précédemment. 

 
If  all  mechanical  error  sources  can  be  excluded  due  to  the  coupling  type  and  the  type  of 
encoder used (e.g. defective encoder mechanics), monitoring the direction of both encoders 
is then sufficient. 
 
This  can  be  run  in  the  Safety  application  using  the  functional  Safety  block 
SF_DirectionMonitor  (see  chapter  “Numeric  Function  Blocks”  in  the  SafetyDesigner  tools 
help) and in this case, performed for both encoders. 

 

If synchronous monitoring is not performed in the Safety application as described 

here, the machine manufacturer must then prove that the requirements of SIL 3 or 

SIL CL 3 according to EN 62061 and PL e, Cat. 4 according to EN ISO 13849-1/-2 are 

met if required for the machine. 

 

Содержание SNC 021

Страница 1: ...SNC 021 S DIAS Safety Incremental Encoder Date of creation 14 11 2017 Version date 02 12 2019 Article number 20 896 021 E...

Страница 2: ...rt of this work may be reproduced edited using an electronic system duplicated or distributed in any form print photocopy microfilm or in any other process without the express permission We reserve th...

Страница 3: ...hannel analysis of the encoder signals with 2 channel error detection of each data line as well as via the measurement of the encoder supply voltages and currents Speed position direction and accelera...

Страница 4: ...ith EU Guidelines 11 2 1 Functional Safety Standards 11 2 2 EU Conformity Declaration 11 2 3 Safety Relevant Parameters 12 2 4 Compatibility 13 3 Technical Data 14 3 1 I encoder Specifications 14 3 2...

Страница 5: ...6 2 Note 23 7 RS422 Interface 23 8 Mounting 24 9 Disposal 25 10 Encoder Configuration 26 11 Installing the Encoder 28 12 Important Notes for Two channel Application 29 13 Supported Cycle Times 31 13 1...

Страница 6: ...risks DANGER DANGER Identifies an immediate danger with high risk which can lead to immediate death or serious injury if not avoided Indique un danger direct haut risque d un d c s imm diat ou des bl...

Страница 7: ...sion lectrique dangereuse Hot surface warning Avertissement d une surface chaude Danger for ESD sensitive components This symbol identifies important or additional information regarding the operation...

Страница 8: ...ince it contains important instructions The technical documentation should be included in the sale rental or transfer of the product Documentation technique Cette documentation technique fait partie i...

Страница 9: ...ail More information on standards and regulations etc can be found in the system handbook Prendre connaissance de consignes de s curit Avant toute manipulation on doit imp rativement prendre connaissa...

Страница 10: ...perate and maintain equipment of functional safety systems and facilities in compliance with the strict guidelines and standards of Safety technology Personnel qualifi Installation montage programmati...

Страница 11: ...e technical data described in this handbook Les modules de s curit sont con us pour une utilisation dans les applications sollicitant un niveau de s curit et r pondent toutes les conditions n cessaire...

Страница 12: ...afety modules This documentation is complete and in readable condition and available at the site of operation Obligation de diligence L utilisateur doit s assurer que les modules de s curit ne sont ut...

Страница 13: ...ms for programmable logic controls 2006 42 EG Directive of the European Parliament and of the Council of 17 May 2006 on Machinery and Change to the Directive 95 16 EC machine guideline 2014 30 EU Elec...

Страница 14: ...e application to determine whether two incremental encoders are sufficient These safety parameters were calculated for the SNC 021 when used with a incremental encoder The safety parameters of the ent...

Страница 15: ...FETY SNC INCREMENTAL ENCODER SNC 021 02 12 2019 Page 13 2 4 Compatibility Compatibility For compatibility of the S DIAS Safety modules see chapter Compatibility of S DIAS Safety Modules in the system...

Страница 16: ...ith monitoring function and current measurement 5 V is generated from 24 V at X3 Status LED yes I encoder current consumption maximum 300 mA per encoder 3 2 Electrical Requirements Supply voltage for...

Страница 17: ...e module de s curit S DIAS Safety est raccord un SCP avec plusieurs modules le courant total des modules de s curit S DIAS utilis s doit tre d termin et v rifi Le courant total de l alimentation 24 V...

Страница 18: ...sea level 0 2000 m without derating 2000 m with derating of the maximum environmental temperature by 0 5 C per 100 m Operating conditions Pollution degree 2 EMC resistance in accordance with 61000 6 7...

Страница 19: ...S DIAS SAFETY SNC INCREMENTAL ENCODER SNC 021 02 12 2019 Page 17 4 Mechanical Dimensions...

Страница 20: ...n 3 and pin 4 are internally bridged To supply the module only one connection to a 24 V pin pin 1 or pin 2 and a GND pin pin 3 or pin 4 is required The bridged connections may be used for further loop...

Страница 21: ...LED can be set to blinking through the visualization so that the module is easily found in the control cabinet OFF BLINKING 2 Hz BLINKING 4 Hz Encoder Status green ON encoder signal OK OFF encoder is...

Страница 22: ...length sleeve length 10 mm Mating direction parallel to the conductor axis or circuit board Conductor cross section rigid 0 2 1 5 mm2 Conductor cross section flexible 0 2 1 5 mm2 conductor cross sect...

Страница 23: ...CODER SNC 021 02 12 2019 Page 21 5 3 Label Field Manufacturer Weidm ller Type MF 10 5 CABUR MC NE WS Article number Weidm ller 1854510000 Compatible printer Weidm ller Type Printjet Advanced 230V Arti...

Страница 24: ...SNC 021 S DIAS SAFETY SNC INCREMENTAL ENCODER Page 22 02 12 2019 6 Wiring 6 1 Wiring Example...

Страница 25: ...d load bearing circuits Protective circuits for all relays RC networks or free wheeling diodes Correct wiring to ground The ground bus should be connected to the control cabinet when possible Si possi...

Страница 26: ...back wall of the control cabinet The individual S DIAS modules are mounted on the DIN rail as a block and secured with latches The modules must be mounted horizontally module label up with sufficient...

Страница 27: ...25 Recommended minimum distances of the S DIAS modules to the surrounding components or control cabinet wall a b c distances in mm inches 9 Disposal For the disposal of the product the respective guid...

Страница 28: ...ctive resolution based on the maximum encoder frequency can be seen Encoder Resolution Increments Conversion Speed Scaling Revolutions Second Revolutions Minute 60 12 500 750 000 80 9 375 562 500 100...

Страница 29: ...ng the position of length units parameter divposition divisor for converting the position of length units parameter mulspeed factor for converting the speed or time base speed multiplier parameter div...

Страница 30: ...er operates without fault During verification which is run via the Set Verified button in the SafetyDesigner or the validation button on the Safe CPU the actual current measurements are used to determ...

Страница 31: ...hn1Speed and S_Chn2Speed synchronous monitoring of the speed of the SNC 021 module The required tolerance must be defined by the user During synchronous monitoring via the position it must be taken in...

Страница 32: ...chrone n est pas effectu e par le logiciel de s curit comme d crit dans la pr sente documentation le constructeur de la machine doit alors prouver que les exigences des normes SIL 3 ou SIL CL 3 selon...

Страница 33: ...times of 250 s to 32 ms If the cycle time is lower than 250 s the IOs are updated with 3 kHz and PDO data are transmitted in a millisecond cycle 13 1 Cycle Times below 1 ms in s 50 100 125 200 250 500...

Страница 34: ...paration 19 02 2019 28 11 Installing the Encoder Tolerance changed from 25 to 25 02 04 2019 12 16 all 2 3 Safety Relevant Parameters 3 4 Environmental Conditions Correction of the safety relevant para...

Страница 35: ...S DIAS SAFETY SNC INCREMENTAL ENCODER SNC 021 02 12 2019 Page 33...

Отзывы: