background image

SNC 021 

S-DIAS SAFETY SNC INCREMENTAL ENCODER 

 

 

Page 28 

02.12.2019 

11  Installing the Encoder 

Line and encoder errors are diagnosed using, among other things, the measurement of the 
encoder currents. 
For this purpose, the preset values for measuring current must be defined in the system. The 
current limits are defined in the automatic system automatically, so the user does not have to 
predefine or configure any additional parameters. 
 
In the unverified status of the system, the encoder currents are measured while starting the 
system and used as temporary reference values. Based on the determined reference values, 
the  current  limits  are  temporarily  defined  with  ±25%.  If  a  corresponding  fluctuation  in  the 
encoder currents due to a wiring fault is detected during movement, the system switches to 
the Safe mode and the appropriate diagnostic codes are provided. 
 

CAUTION! 

Before the Safety system is labeled as verified, the wiring of the installed encoder must be 
checked  manually  to  ensure  that  the  system  operates  error-free  (the  encoder  operates 
without fault).  
 
During  verification,  which  is 

run  via  the  “Set  Verified”  button  in  the  SafetyDesigner  or  the 

validation button on the Safe CPU, the actual current measurements are used to determine 
the permissible limit values for the encoder current and then stored in the Safe CPUs remnant 
data. These limit values are based on the measured value ±25 %. 
 
After  successful  validation,  the  encoder  currents  are  monitored  using  the  current  values 
stored in the Safe CPU. When in verified status, the upper or lower limits are exceeded, the 
system changes to safe mode and the appropriate diagnostic code for error analysis is again 
provided. 
 
In  the  standard  application,  the  actual  and  preset  current  values  are  provided  via  the 
hardware classes. 
 

CAUTION!

 

Exchanging the encoder 

Basically, the Safety system cannot detect an encoder exchange when no power is applied. 
The parameters of the new encoder could be different from the replaced encoders with regard 
to the currents, whereby it is no longer possible guarantee the appropriate monitoring of the 
newly installed encoder. 
 
In such a case, the system 

must

 be reverified. This means reconfiguring the Safe CPU via 

the SafetyDesigner or µSD card and verifying (see Safety System manual) 
 

 

Содержание SNC 021

Страница 1: ...SNC 021 S DIAS Safety Incremental Encoder Date of creation 14 11 2017 Version date 02 12 2019 Article number 20 896 021 E...

Страница 2: ...rt of this work may be reproduced edited using an electronic system duplicated or distributed in any form print photocopy microfilm or in any other process without the express permission We reserve th...

Страница 3: ...hannel analysis of the encoder signals with 2 channel error detection of each data line as well as via the measurement of the encoder supply voltages and currents Speed position direction and accelera...

Страница 4: ...ith EU Guidelines 11 2 1 Functional Safety Standards 11 2 2 EU Conformity Declaration 11 2 3 Safety Relevant Parameters 12 2 4 Compatibility 13 3 Technical Data 14 3 1 I encoder Specifications 14 3 2...

Страница 5: ...6 2 Note 23 7 RS422 Interface 23 8 Mounting 24 9 Disposal 25 10 Encoder Configuration 26 11 Installing the Encoder 28 12 Important Notes for Two channel Application 29 13 Supported Cycle Times 31 13 1...

Страница 6: ...risks DANGER DANGER Identifies an immediate danger with high risk which can lead to immediate death or serious injury if not avoided Indique un danger direct haut risque d un d c s imm diat ou des bl...

Страница 7: ...sion lectrique dangereuse Hot surface warning Avertissement d une surface chaude Danger for ESD sensitive components This symbol identifies important or additional information regarding the operation...

Страница 8: ...ince it contains important instructions The technical documentation should be included in the sale rental or transfer of the product Documentation technique Cette documentation technique fait partie i...

Страница 9: ...ail More information on standards and regulations etc can be found in the system handbook Prendre connaissance de consignes de s curit Avant toute manipulation on doit imp rativement prendre connaissa...

Страница 10: ...perate and maintain equipment of functional safety systems and facilities in compliance with the strict guidelines and standards of Safety technology Personnel qualifi Installation montage programmati...

Страница 11: ...e technical data described in this handbook Les modules de s curit sont con us pour une utilisation dans les applications sollicitant un niveau de s curit et r pondent toutes les conditions n cessaire...

Страница 12: ...afety modules This documentation is complete and in readable condition and available at the site of operation Obligation de diligence L utilisateur doit s assurer que les modules de s curit ne sont ut...

Страница 13: ...ms for programmable logic controls 2006 42 EG Directive of the European Parliament and of the Council of 17 May 2006 on Machinery and Change to the Directive 95 16 EC machine guideline 2014 30 EU Elec...

Страница 14: ...e application to determine whether two incremental encoders are sufficient These safety parameters were calculated for the SNC 021 when used with a incremental encoder The safety parameters of the ent...

Страница 15: ...FETY SNC INCREMENTAL ENCODER SNC 021 02 12 2019 Page 13 2 4 Compatibility Compatibility For compatibility of the S DIAS Safety modules see chapter Compatibility of S DIAS Safety Modules in the system...

Страница 16: ...ith monitoring function and current measurement 5 V is generated from 24 V at X3 Status LED yes I encoder current consumption maximum 300 mA per encoder 3 2 Electrical Requirements Supply voltage for...

Страница 17: ...e module de s curit S DIAS Safety est raccord un SCP avec plusieurs modules le courant total des modules de s curit S DIAS utilis s doit tre d termin et v rifi Le courant total de l alimentation 24 V...

Страница 18: ...sea level 0 2000 m without derating 2000 m with derating of the maximum environmental temperature by 0 5 C per 100 m Operating conditions Pollution degree 2 EMC resistance in accordance with 61000 6 7...

Страница 19: ...S DIAS SAFETY SNC INCREMENTAL ENCODER SNC 021 02 12 2019 Page 17 4 Mechanical Dimensions...

Страница 20: ...n 3 and pin 4 are internally bridged To supply the module only one connection to a 24 V pin pin 1 or pin 2 and a GND pin pin 3 or pin 4 is required The bridged connections may be used for further loop...

Страница 21: ...LED can be set to blinking through the visualization so that the module is easily found in the control cabinet OFF BLINKING 2 Hz BLINKING 4 Hz Encoder Status green ON encoder signal OK OFF encoder is...

Страница 22: ...length sleeve length 10 mm Mating direction parallel to the conductor axis or circuit board Conductor cross section rigid 0 2 1 5 mm2 Conductor cross section flexible 0 2 1 5 mm2 conductor cross sect...

Страница 23: ...CODER SNC 021 02 12 2019 Page 21 5 3 Label Field Manufacturer Weidm ller Type MF 10 5 CABUR MC NE WS Article number Weidm ller 1854510000 Compatible printer Weidm ller Type Printjet Advanced 230V Arti...

Страница 24: ...SNC 021 S DIAS SAFETY SNC INCREMENTAL ENCODER Page 22 02 12 2019 6 Wiring 6 1 Wiring Example...

Страница 25: ...d load bearing circuits Protective circuits for all relays RC networks or free wheeling diodes Correct wiring to ground The ground bus should be connected to the control cabinet when possible Si possi...

Страница 26: ...back wall of the control cabinet The individual S DIAS modules are mounted on the DIN rail as a block and secured with latches The modules must be mounted horizontally module label up with sufficient...

Страница 27: ...25 Recommended minimum distances of the S DIAS modules to the surrounding components or control cabinet wall a b c distances in mm inches 9 Disposal For the disposal of the product the respective guid...

Страница 28: ...ctive resolution based on the maximum encoder frequency can be seen Encoder Resolution Increments Conversion Speed Scaling Revolutions Second Revolutions Minute 60 12 500 750 000 80 9 375 562 500 100...

Страница 29: ...ng the position of length units parameter divposition divisor for converting the position of length units parameter mulspeed factor for converting the speed or time base speed multiplier parameter div...

Страница 30: ...er operates without fault During verification which is run via the Set Verified button in the SafetyDesigner or the validation button on the Safe CPU the actual current measurements are used to determ...

Страница 31: ...hn1Speed and S_Chn2Speed synchronous monitoring of the speed of the SNC 021 module The required tolerance must be defined by the user During synchronous monitoring via the position it must be taken in...

Страница 32: ...chrone n est pas effectu e par le logiciel de s curit comme d crit dans la pr sente documentation le constructeur de la machine doit alors prouver que les exigences des normes SIL 3 ou SIL CL 3 selon...

Страница 33: ...times of 250 s to 32 ms If the cycle time is lower than 250 s the IOs are updated with 3 kHz and PDO data are transmitted in a millisecond cycle 13 1 Cycle Times below 1 ms in s 50 100 125 200 250 500...

Страница 34: ...paration 19 02 2019 28 11 Installing the Encoder Tolerance changed from 25 to 25 02 04 2019 12 16 all 2 3 Safety Relevant Parameters 3 4 Environmental Conditions Correction of the safety relevant para...

Страница 35: ...S DIAS SAFETY SNC INCREMENTAL ENCODER SNC 021 02 12 2019 Page 33...

Отзывы: