background image

ETV 0853-3 

CONTROL PANEL  

 

Page 22 

12.04.2017 

 

Status and Error Messages 

 
Status  and  error  messages  are  displayed  in  the  LASAL  Class  software  status  test. 
POINTER or CHKSUM messages can also be shown on the terminal screen. 
 

Number

 

Message 

Definition 

Cause/solution 

00 

RUN RAM 

The user program is currently running in 
RAM. 

The display is not affected. 

Info 

01

 

RUN ROM 

The user program in the program 

memory module was loaded into the 

RAM and is currently being run. 

The display is not affected. 

Info 

02 

RUNTIME 

The total duration of all cyclic objects 
exceeds the maximum time; the time can 
be configured using 2 system variables: 

Runtime: time remaining 

SWRuntime: pre-selected value for the 
runtime counter 

Optimize the application's cyclic 
task. 

Use

 

higher

 

capacity

 

CPU

 

Configure preset value 

03 

POINTER 

Incorrect program pointers were detected 
before running the user program 

Possible Causes: 

The program memory module is 
missing, not programmed or de-
fect. 

The program in the user program 
memory (RAM) is not executable. 

The buffering battery has failed. 

The user program has overwritten 
a software error. 

  

Solution: 

Reprogram the memory module, 
if the error reoccurs exchange the 
module. 

Exchange the buffering battery 

Correct programming error 

04 

CHKSUM 

Before running the user program, a false 
checksum was detected. 

Cause/solution: s. POINTER 

Содержание ETV 0853-3

Страница 1: ...screen serves as the input medium for process data and parameters The output is shown on an 8 4 SVGA TFT color display With the LSE mask editor graphics can be created on the PC then stored and displa...

Страница 2: ...tion 18 Shielding 18 ESD Protection 18 USB Interface Connections 18 CAN Bus Setup 19 CAN Bus Termination 20 Process Diagram 21 Status and Error Messages 22 Application exceptions 30 Note on SRAM Behav...

Страница 3: ...nternal I O Yes Interface connections 1x USB 2 0 Type A Full speed 12 Mbit s 1x USB 1 1 Type Mini B 1x Ethernet 1x VARAN bus maximum length 100 m 1x CAN bus Internal interface connections and devices...

Страница 4: ...ted either a max 5 amps for voltages 0 20 V 0 28 3 Vp or b 100 VA Vp for voltages of 20 30 V 28 3 42 4 Vp Terminal Dimensions 220 x 172 x 33 7 mm W x H x D Material Front plate 4 mm black anodized alu...

Страница 5: ...ouch panel Surface 0 7 mm front glass with black frame Cleaning See Chapter Cleaning the Touch Screen The ETV 0853 3 has a projective capacitive touch screen is built in with which 2 finger input Zoom...

Страница 6: ...active 1 V Residual output current inactive 12 A Turn on delay 400 s Turn off delay 400 s Max braking energy of inductive loads 1 channel 0 12 Joules Digital Inputs Number of 8 Input voltage Typicall...

Страница 7: ...lots No erosive cleaning solutions chemicals abrasive cleansers or hard objects that can scratch or damage the touch screen may be used Since it may be possible to activate the touch screen by water d...

Страница 8: ...ETV 0853 3 CONTROL PANEL Page 8 12 04 2017 Mechanical Dimensions...

Страница 9: ...2017 Page 9 Connector Layout Connections on Rear and Bottom X1 Power plug X2 CAN Pin Function 1 24 V DC DIG IOs 2 24 V DC 3 GND 4 GND Pin Function 1 CAN A CAN LOW 2 CAN B High 3 CAN A CAN LOW 4 CAN B...

Страница 10: ...ital inputs 8 digital outputs Pin Function 1 OUTPUT 1 2 OUTPUT 2 3 OUTPUT 3 4 OUTPUT 4 5 Input 1 6 Input 2 7 Input 3 8 Input 4 Pin Function 1 OUTPUT 5 2 OUTPUT 6 3 OUTPUT 7 4 OUTPUT 8 5 Input 5 6 Inpu...

Страница 11: ...use a real time runtime error or runtime error By configuring the packet filter Firewall or Router accordingly however it is possible to connect a network with SIGMATEK hardware to a third party netwo...

Страница 12: ...the market do not comply with USB specifications this can lead to device malfunctions It is also possible that these devices will not be detected at the USB port or function correctly Therefore it is...

Страница 13: ...arte microSD 1 Go Edge est le 12 630 101 Le nombre de cycles de lecture et d criture a l influence notable sur la dur e de vie des supports de stockage Applicable connectors CAN Bus 6 pin Weidm ller p...

Страница 14: ...um battery is installed at the manufacturer The battery has enough capacity to preserve data in the absence of a supply voltage for up to 7 years Battery order number 01 690 055 MANUFACTURER DATA Lith...

Страница 15: ...CONTROL PANEL ETV 0853 3 12 04 2017 Page 15 Exchanging the Battery 1 Disconnect the power to the ETV 2 Open the locking screws on the back f the terminal with a 6 edge screwdriver 2 mm...

Страница 16: ...3 CONTROL PANEL Page 16 12 04 2017 4 Using the strap remove the battery from the holder see arrow 5 Place the new battery in the holder with the correct polarity Pole toward the frontside and replace...

Страница 17: ...ooling The terminal s power loss can reach up to 10 Watts To ensure the necessary air circula tion for cooling the following mounting instructions must be followed Mounting Instructions The following...

Страница 18: ...hrough the RJ45 connector Noise therefore cannot reach the electronics and affect the function ESD Protection Typically USB devices keyboard mouse are not equipped with shielded cables These devices a...

Страница 19: ...31 stations can be in stalled in a CAN bus system However each station number can only be assigned once CAN bus data transfer rate The data transfer rate baud rate for the CAN bus can be set However...

Страница 20: ...mission errors caused by reflections in the line Device 1 Device 2 Device 3 Device n e g CPU DCP 160 e g Terminal ET 081 CAN bus connection CAN bus termination on the clamp module DSUB plug with termi...

Страница 21: ...CONTROL PANEL ETV 0853 3 12 04 2017 Page 21 Process Diagram...

Страница 22: ...time the time can be configured using 2 system variables Runtime time remaining SWRuntime pre selected value for the runtime counter Optimize the application s cyclic task Use higher capacity CPU Con...

Страница 23: ...7 PROM DEFECT An error has occurred while program ming the memory module Cause The program memory module is defect The user program is too large The program memory module is missing Solution Exchange...

Страница 24: ...n Correct programming error 18 SINGLE STEP The CPU is in single step mode and is waiting for further instructions Info 19 Ready A module or project has been sent to the CPU and it is ready to run the...

Страница 25: ...t report error to Sigmatek 31 SEARCH FOR OS The boot loader is searching for the operating system in RAM Restart report error to Sigmatek 32 NO DEVICE Reserved 33 UNUSED CODE Reserved 34 MEM ERROR The...

Страница 26: ...the NULL pointer Solution Correct application errors 51 BOUND EXCEEDED An exception error has occurred when accessing arrays The memory area was overwritten through accessing an invalid element Solut...

Страница 27: ...Optimize the application s back ground task background Use higher capacity CPU Set SWBTRuntime correctly 70 C DIAS ERROR An error occurred in connection with a C DIAS module Cause The reason for this...

Страница 28: ...le all and reload project components 113 C_NO_FILE_OPEN An attempt was made to open an un known table 114 C_OUTOF_NEAR Memory allocation error 115 C_OUT OF_FAR Memory allocation error 116 C_INCOMAPTIB...

Страница 29: ...L ETV 0853 3 12 04 2017 Page 29 241 REBOOT The operating system is restarted 242 LSL SAVE 243 LSL LOAD 252 CONTINUE 253 PRERUN The application is started 254 PRERESET The application is ended 255 CONN...

Страница 30: ...the user program is writing to the Micro SD card this can sometimes lead to partial loss of remnant data The file system does not support safe writing through SRAM If files are stored modified or writ...

Страница 31: ...r program can have a massive effect on the microSD card lifespan Detailed information regarding the SRAM behavior and the corresponding settings can be found in the LASAL OS documentation in the chapt...

Страница 32: ...ions in which the bus is run outside the control cabinet the correct shielding is required Especially when for structural reasons the bus line must be placed next to strong electromagnetic interferenc...

Страница 33: ...rnal VARAN Component If the Ethernet lines are connected from a VARAN component to a VARAN node located outside the control cabinet the shielding should be placed at the entry point to the control cab...

Страница 34: ...additional shield connection is required This requires that only IP67 modules and connectors be used These components are very robust and noise resistant The shielding for all sockets in IP67 modules...

Страница 35: ...etc can induce interference in a VARAN bus line Voltage spikes are dissipated over the metallic housing of a RJ45 connector Noise is conducted over the control cabinet without additional measures need...

Страница 36: ...4 Connecting Noise Generating Components When connecting power lines to the bus that generate strong electromagnetic noise the correct shielding is also important The shielding should be placed before...

Страница 37: ...etween Two Control Cabinets If two control cabinets must be connected over a VARAN bus it is recommended that the shielding be located at the entry points of each cabinet Noise is therefore prevented...

Страница 38: ...ETV 0853 3 CONTROL PANEL Page 38 12 04 2017...

Отзывы: