Sigineer Power MCRLCD Скачать руководство пользователя страница 21

 

 

 

19

 

39 

Charge over current 

Beep once every second 

 

40 

Discharge over temperature 

Beep once every second 

 

41 

Charge over temperature 

Beep once every second 

 

42 

Mosfet over temperature 

Beep once every second 

 

43 

Battery over temperature 

Beep once every second 

 

44 

Battery under temperature 

Beep once every second 

 

45 

System shut down 

Beep once every second 

 

 
 

TroubleShooting 

 

Problem 

LCD/LED/Buzzer 

Explanation   

What to do 

Unit shuts down 

Automatically during   

startup process. 

LCD/LEDs and buzzer will   

be active for 3 seconds   

and then    complete off. 

The battery voltage is too low . 

(<1.91V/Cell) 

1.Re-charge battery. 

2.Replace battery. 

No response after   

power on. 

No indication. 

1.The battery voltage is far too   

low. (<1.4V/Cell) 

2.Battery polarity is connected   

reversed. 

1.

 

Check if batteries and the wiring are connected well. 

2.Re-charge battery. 

3.Replace battery. 

Mains exist but the   

unit works in battery   

mode. 

Input voltage is 0 on the   

LCD and green LED is   

flashing. 

Input protector is tripped. 

Check if AC breaker is tripped and AC wiring is   

connected well. 

Green LED is flashing. 

Insufficient quality of AC power. 

(Shore or Generator) 

1.

 

Check if AC wires are too thin and/or too long. 

2.

 

Check if generator (if applied) is working well or if   

input voltage range setting is correct.   
(UPS→Appliance) 

Green LED is flashing. 

Set “Battery First”    or “Solar First”   

as the priority of output source. 

Change output source priority to Utility first. 

When it’s turned on,   

internal relay is 

switching on and off   

repeatedly. 

LCD display and LEDs are   

flashing 

Battery is disconnected. 

Check if battery wires are connected well. 

Buzzer beeps   

continuously and red   

LED is on.(Fault code) 

 

Buzzer beeps once   

every second, and red 

LED is flashing. 

(Warning code) 

Fault code 01 

Fan fault. 

1.Check whether all fans are working properly. 

2.Replace the fan. 

Fault code 02 

Internal temperature of component   

is over 100℃. 

1.Check whether the air flow of the unit is blocked or   

whether the ambient temperature is too high. 

2.Check whether the thermistor plug is loose. 

Fault code 03 

Battery is over-charged. 

Restart the unit, if the error happens again, please   

return to repair center. 

The battery voltage is too high. 

Check if spec and quantity of batteries are meet   

requirements. 

Warning code 04 

The battery voltage/SOC is too low. 

1.Measure battery voltage in DC input. 

2.Check battery SOC in LCD when use Li battery. 

3.Recharge the battery. 

Fault code 05 

Output short circuited. 

Check if wiring is connected well and remove   

abnormal load. 

Содержание MCRLCD

Страница 1: ...s Manual For Solar Inverter Models M3024NC M3048NC M3048BP M5000H 48BP M6048DUL M12048DUL etc Version 1 0 PN MCRLCD220509 Manufacturer Information Sigineer Power Limited Email info sigineer com TEL 8...

Страница 2: ...ecting to Inverter 4 2 6 LCD Specification Setup 4 4 Maintenance Troubleshooting 16 5 Warranty 20 Please record the Sigineer Power unit s model and serial number in case you need to provide this infor...

Страница 3: ...use this remote LCD panel on other equipments it is designed only to work with Sigineer Power solar inverters produced after 2022 May 2 Don t use any third party communication cables on the panel 3 D...

Страница 4: ...ection Unit x1 User manual x 1 Communication cable 20m 65 6ft x 1 2 4 Installation There are two pieces of flanges which can be flexibly installed either on the panel top or two sides Surface Mounting...

Страница 5: ...3 Flush Mounting with Flange on the Sides...

Страница 6: ...el area includes three LED indicators four function keys and a LCD display It shows very rich operating info 1 LCD display 2 Status indicator 3 Charging indicator 4 Fault indicator 5 Function buttons...

Страница 7: ...ppened Indicate short circuit happened Battery Information Indicate battery level by 0 24 25 49 50 74 and 75 100 in battery mode and charging status in line mode Indicate battery voltage battery perce...

Страница 8: ...wer Indicates the utility charger circuit is working Indicates the DC AC inverter circuit is working These three signs indicate the output priority SOL FIRST indicates solar first BAT FIRST indicates...

Страница 9: ...Utility Battery In this mode the inverter will transfer between DC and AC as per the settings of program 12 and 13 Users can set it to utility priority to stop the cycling 01 SbU SBU Priority As indi...

Страница 10: ...P 95 140Vac 7V M5000H 48BP 170 280VAC 7V M6048DUL M12048DUL 184 272Vac 7V 03 GEN In Generator Mode the acceptable AC input voltage range M3024NC M3048NC M3048BP 65 140Vac 7V M5000H 48BP 90 280VAC 7V M...

Страница 11: ...only when the battery voltage changes big enough Due to the ripple current from the utility charger when US2 is set for charging lithium batteries it is recommended to set the max utility charging cur...

Страница 12: ...nt is set according to Program 02 for utility charger Program 12 DC to AC Transfer Voltage The setting works when program 01 is in SBU Priority or Solar Priority Mode Model Default Value Resettable Ra...

Страница 13: ...the charger Program 20 Float Charging Voltage Model Default Value Resettable Range 48V Models 54V 48V 58 4V If user defined setting USE US2 is selected in program 5 this program can be set up Program...

Страница 14: ...Charging Current Max PV Utility Charging Current 03 AC Input Voltage Range Appliance Mode Default 03 AC Input Voltage Range UPS Mode 03 AC Input Voltage Range Generator mode 04 Power Saving Mode Savi...

Страница 15: ...rity Solar Priority 14 Charger Power Source Priority Solar and Utility Default 14 Charger Power Source Priority Solar Only 15 Alarm On Off Control Audible Alarm on default 15 Alarm On Off Control Audi...

Страница 16: ...oltage Load percentage PV input voltage Battery voltage Warning or Fault code Default Display Screen AC Input frequency Output frequency Load power in VA PV energy sum in KWH Battery percentage Warnin...

Страница 17: ...erter can charge battery without AC output Power saving mode If enabled the output of inverter will be off when connected load is two low or not detected No output is supplied by the unit but it still...

Страница 18: ...rger switch to DC to AC model The M5000H 48BP inverters can be stacked up to 6 pcs to expand output power in 230Vac or create 230 400Vac three phase The M3048BP can be stacked up to 6 pcs to expand ou...

Страница 19: ...9 Bus soft start failed 51 Over current or surge 52 Bus voltage is too low 53 Inverter soft start failed 55 Over DC voltage in AC output 56 Battery connection is open 57 Current sensor failed 58 Outpu...

Страница 20: ...Beep once every second 16 Parallel input phase error Beep once every second 17 Parallel output phase loss Beep once every second 18 Buck over current Beep once every second 19 Battery disconnect No b...

Страница 21: ...es are too thin and or too long 2 Check if generator if applied is working well or if input voltage range setting is correct UPS Appliance Green LED is flashing Set Battery First or Solar First as the...

Страница 22: ...ery is not connected well or fuse is burnt If the battery is connected well please return to repair center Fault code 60 Negative power fault 1 Check whether the AC output connected to the grid input...

Страница 23: ...lly or externally or damaged from improper use or use in an unsuitable environment violations of the warnings in the manual will invalid the warranty b the product if it has been subjected to fire wat...

Отзывы: