12
When the Program 12: DC to AC Transfer Voltage value is already set, the Program 21: Low Battery
Cut-Off Voltage value must be lower than that. When the two values conflicts, the value in program 21 will
automatically revert back.
Program #
Description
ICON
01 Power Priority for AC
Loads
Utility Priority
01 Power Priority for AC
Loads
Solar Priority
01 Power Priority for AC
Loads
SBU Priority
01 Power Priority for AC
Loads
SUB Priority
02 Maximum Charging
Current
Max PV+Utility
Charging Current
03 AC Input Voltage Range
Appliance Mode
(Default)
03 AC Input Voltage Range
UPS Mode
03 AC Input Voltage Range
Generator mode
04: Power Saving Mode
Saving mode disable
(Default)
04: Power Saving Mode
Saving mode enable
05 Battery Type
AGM Battery (Default)
05 Battery Type
Flood Battery
05 Battery Type
User-Defined
05 Battery Type
User-Defined 2
05 Battery Type
Lithium
06 Automatic Overload Restart Restart Disable (Default)
06 Automatic Overload Restart
Restart Enable
07 Automatic OverTemp
Restart
Restart Disable (Default)
07 Automatic OverTemp
Restart
Restart Enable
08 AC Output Voltage
230V (Default)