Program 09: AC Output Frequency
The AC Output Frequency can be set to 50Hz or 60Hz.
Program 10: Number of 12V Batteries Connected In Series
The default value is 4. This program is only a reminder about the 12V battery quantity.
Program 11: Maximum Utility Charging Current
Model #
Default Value
Resettable Range
M3024NC
30A
0-60A
M3048NC
30A
0-40A
M3048BP
30
A
0-40A
M5000H-48BP
30A
0-80A
M6048DUL
30A
10-60A
M12048DUL
30A
10-100A
The solar charger has higher priority than the utility charger, if the max charging current and utility charger
is set to the same value, the solar charger will still work.
If setting value in Program 02 is smaller than that in Program 11, the final charging current is set according
to Program 02 for utility charger.
Program 12 DC to AC Transfer Voltage
The setting works when program 01 is in “SBU Priority” or “Solar Priority” Mode.
Model #
Default Value
Resettable Range
48V models
46V/50%
44V~51.2V/6%-95%
The battery SOC will be displayed when BMS communication is established.
Half for 24Vdc model.
Program 13 AC to DC Transfer Voltage
The setting works when program 01 is in “SBU Priority” or “Solar Priority” Mode.
Model #
Default Value
Resettable Range
48V models
54V/95%
48V~58V/10%-100%
The battery SOC will be displayed when BMS communication is established.
Half for 24Vdc model.
Program 14 Charge Power Source Priority
14:CSO
Solar Priority
Solar energy will charge battery as the first priority.
Utility will charge battery only when solar energy is not available (lost).
14:SNU
Solar and Utility (Default)
Solar energy and utility will both charge battery.
14:OSO