13

 

09 AC Output Frequency 

50Hz (Default) 

     

 

10 Number of 12V Batteries 
Connected In Series 

The default value is 4 for 
48V model, and 2 for 
24Vdc model. 

     

 

11 Maximum Utility Charging 
Current 

10A to Max(default 30A) 

     

 

12 DC to AC Transfer Voltage    Default 46.0V, 

44.0V~51.2V resettable, 

     

 

12 DC to AC Transfer Voltage  Lithium mode: default 

40%, 5%~50% resettable 

   

 

13 AC to DC Transfer Voltage  Default 54.0V, 

48.0V~58.0V resettable, 

       

 

13 AC to DC Transfer Voltage  Li mode: default 80%, 

60%~100% resettable 

     

 

14 Charger Power Source 
Priority 

Solar Priority 

       

 

14  Charger  Power  Source 
Priority 

Solar and Utility 
(Default) 

       

 

14  Charger  Power  Source 
Priority 

Solar Only 

     

 

15 Alarm On/Off Control 

Audible Alarm on 
(default) 

       

 

15 Alarm On/Off Control 

Audible Alarm off(Mute) 

       

 

16 Backlight On/Off Control 

Backlight on (default) 

       

 

16 Backlight On/Off Control 

Backlight off   

       

 

17 Beeps once between AC 
and DC Transfer 

Alarm on (default) 

       

 

17 Beeps once between AC 
and DC Transfer 

Alarm off 

       

 

18 Overload Bypass 

Bypass Disable 

(default) 

       

 

18 Overload Bypass 

Bypass enable 

       

 

19 C.V. Charging Voltage 

48V model: default 
56.4V, 48.0V~58.4V 
Settable   

       

 

20 Float Charging Voltage 

 

       

 

21 Low Battery Cut-Off 
Voltage 

Without BMS 
communication 

       

 

21 Low Battery Cut-Off 
Voltage 

With BMS 
communication 

     

 

 

Содержание MCRLCD

Страница 1: ...s Manual For Solar Inverter Models M3024NC M3048NC M3048BP M5000H 48BP M6048DUL M12048DUL etc Version 1 0 PN MCRLCD220509 Manufacturer Information Sigineer Power Limited Email info sigineer com TEL 8...

Страница 2: ...ecting to Inverter 4 2 6 LCD Specification Setup 4 4 Maintenance Troubleshooting 16 5 Warranty 20 Please record the Sigineer Power unit s model and serial number in case you need to provide this infor...

Страница 3: ...use this remote LCD panel on other equipments it is designed only to work with Sigineer Power solar inverters produced after 2022 May 2 Don t use any third party communication cables on the panel 3 D...

Страница 4: ...ection Unit x1 User manual x 1 Communication cable 20m 65 6ft x 1 2 4 Installation There are two pieces of flanges which can be flexibly installed either on the panel top or two sides Surface Mounting...

Страница 5: ...3 Flush Mounting with Flange on the Sides...

Страница 6: ...el area includes three LED indicators four function keys and a LCD display It shows very rich operating info 1 LCD display 2 Status indicator 3 Charging indicator 4 Fault indicator 5 Function buttons...

Страница 7: ...ppened Indicate short circuit happened Battery Information Indicate battery level by 0 24 25 49 50 74 and 75 100 in battery mode and charging status in line mode Indicate battery voltage battery perce...

Страница 8: ...wer Indicates the utility charger circuit is working Indicates the DC AC inverter circuit is working These three signs indicate the output priority SOL FIRST indicates solar first BAT FIRST indicates...

Страница 9: ...Utility Battery In this mode the inverter will transfer between DC and AC as per the settings of program 12 and 13 Users can set it to utility priority to stop the cycling 01 SbU SBU Priority As indi...

Страница 10: ...P 95 140Vac 7V M5000H 48BP 170 280VAC 7V M6048DUL M12048DUL 184 272Vac 7V 03 GEN In Generator Mode the acceptable AC input voltage range M3024NC M3048NC M3048BP 65 140Vac 7V M5000H 48BP 90 280VAC 7V M...

Страница 11: ...only when the battery voltage changes big enough Due to the ripple current from the utility charger when US2 is set for charging lithium batteries it is recommended to set the max utility charging cur...

Страница 12: ...nt is set according to Program 02 for utility charger Program 12 DC to AC Transfer Voltage The setting works when program 01 is in SBU Priority or Solar Priority Mode Model Default Value Resettable Ra...

Страница 13: ...the charger Program 20 Float Charging Voltage Model Default Value Resettable Range 48V Models 54V 48V 58 4V If user defined setting USE US2 is selected in program 5 this program can be set up Program...

Страница 14: ...Charging Current Max PV Utility Charging Current 03 AC Input Voltage Range Appliance Mode Default 03 AC Input Voltage Range UPS Mode 03 AC Input Voltage Range Generator mode 04 Power Saving Mode Savi...

Страница 15: ...rity Solar Priority 14 Charger Power Source Priority Solar and Utility Default 14 Charger Power Source Priority Solar Only 15 Alarm On Off Control Audible Alarm on default 15 Alarm On Off Control Audi...

Страница 16: ...oltage Load percentage PV input voltage Battery voltage Warning or Fault code Default Display Screen AC Input frequency Output frequency Load power in VA PV energy sum in KWH Battery percentage Warnin...

Страница 17: ...erter can charge battery without AC output Power saving mode If enabled the output of inverter will be off when connected load is two low or not detected No output is supplied by the unit but it still...

Страница 18: ...rger switch to DC to AC model The M5000H 48BP inverters can be stacked up to 6 pcs to expand output power in 230Vac or create 230 400Vac three phase The M3048BP can be stacked up to 6 pcs to expand ou...

Страница 19: ...9 Bus soft start failed 51 Over current or surge 52 Bus voltage is too low 53 Inverter soft start failed 55 Over DC voltage in AC output 56 Battery connection is open 57 Current sensor failed 58 Outpu...

Страница 20: ...Beep once every second 16 Parallel input phase error Beep once every second 17 Parallel output phase loss Beep once every second 18 Buck over current Beep once every second 19 Battery disconnect No b...

Страница 21: ...es are too thin and or too long 2 Check if generator if applied is working well or if input voltage range setting is correct UPS Appliance Green LED is flashing Set Battery First or Solar First as the...

Страница 22: ...ery is not connected well or fuse is burnt If the battery is connected well please return to repair center Fault code 60 Negative power fault 1 Check whether the AC output connected to the grid input...

Страница 23: ...lly or externally or damaged from improper use or use in an unsuitable environment violations of the warnings in the manual will invalid the warranty b the product if it has been subjected to fire wat...

Отзывы: