If the Verify Relay is configured for “Non-Latching” then it will
reset to normal when the detector no longer sees a verified fire for
a period of time (factory default is 3 seconds).
Pins on the "J3" connector labeled “Verify In” and “Verify Out”
provide connections for Normally Open contacts on the -HE1 and
-HE3 models or Normally Closed contacts on the -HE2 and -HE4
models.
Model
Verify Relay
Aux. Relay
RED1-HST
N/A
N/A
RED1-HNT
N/A
N/A
RED1-HE1
Open Contacts
Closed Contacts
RED1-HE2
Closed Contacts
Open Contacts
RED1-HE3
Open Contacts
Open Contacts
RED1-HE4
Closed Contact
Closed Contacts
2.7.4 Aux. Relay
The Aux. Relay is energized whenever the detector fails the UV
self test. This fault indicates degradation in the detectors ability to
“see” a fire. Normally, cleaning the lens will clear this fault. This
condition normally occurs when there is an oily lens or a
malfunctioning UV sensor. The Pins on the "J3" connector (see
section on Connectors) labeled “Aux In” and “Aux Out” provide
connections for a Normally Open contact on the -HE2 and -HE3
models or a Normally Closed contact on the -HE1 and -HE4
models.
3. Installation
3.1 Housing and Conduit
3.1.1 Mounting the Housing
The housing is mounted by using the two .3” diameter holes
located in ears on the back of the housing. The two conduit holes
located on the side of the housing are not to be used for
mounting. The detector should be mounted securely to a flat
surface. The mounting location must be strong enough to support
the detectors weight. Although the detector is not vibration
sensitive the detector should not be exposed to excessive
vibration. The detector has been tested to .022” displacement, 10
Hz to 30 Hz sweep cycled at 2 cpm for 4 hours.
3.1.2 Installing the Conduit and Wiring
Mount a “Seal Off” at the housing into the 3/4” NPT conduit
opening(s) located on either side of the housing. Connect the
conduit to the “Seal Off”. If one of the conduit openings is not
used insert a sealing plug into the unused opening. Run the wires
through the conduit, “Seal Off”, and into the housing. The ends of