![Sierra RED1-HE1 Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/sierra/red1-he1/red1-he1_installation-manual_1266477017.webp)
Sierra Safety Technology, Inc.
www.sierrasafety.com
All rights reserved - © 2016
Page 15 of 20
7. Tables
7.1 Dip Switch Settings
7.1.1 Sensitivity
Sensitivity
SW1 SW2 Level
20 Foot
ON
ON
4
40 Foot
OFF
ON
3
60 Foot
ON
OFF
2
80 Foot
OFF
OFF
1
7.1.2 Verify Control (-HE1 to -HE4 Models only)
Verify
Description
SW3 SW4 SW5
Level 0
Verify = Fire
OFF
OFF
OFF
Level 1
Min. Verify (shorter)
ON
OFF
OFF
Level 2
OFF
ON
OFF
Level 3
ON
ON
OFF
Level 4
OFF
OFF
ON
Level 5
ON
OFF
ON
Level 6
Max. Verify (longer)
OFF
ON
ON
Level 7
Verify Disabled
ON
ON
ON
7.1.3 Fire Relay “Latching” Control
Fire Relay
Description
SW6
Latching
Alarm Until Power Down Reset
OFF
Non-Latching
Alarm Until No Fire (.5 to 10 sec.)
ON
7.1.4 Verify Relay “Latching” Control (HE1 to HE4 Models only)
Verify Relay
Description
SW7
Latching
Alarm Until Power Down Reset
OFF
Non-Latching
Alarm Until No Fire (.5 to 10 sec.)
ON
SW6 and SW7 must be ON for the Verify Relay to be
“Non-Latching”.
7.1.5 Detector “Latching” Control
Detector
Description
SW8
Latching
Alarm Until Power Down Reset
OFF
Non-Latching
Alarm Until No Fire
ON
SW6, SW7, and SW8 must be ON for the Detector to be
“Non-Latching”.