![Sierra RED1-HE1 Скачать руководство пользователя страница 18](http://html.mh-extra.com/html/sierra/red1-he1/red1-he1_installation-manual_1266477018.webp)
Sierra Safety Technology, Inc.
www.sierrasafety.com
All rights reserved - © 2016
Page 16 of 20
7.1.6 High Speed Disable
High Speed
Description
SW9
Enabled
50 Millisecond Response to a 1” High
Butane Flame at 12 Inches
OFF
Disabled
5 Second Response to Standard Fire
ON
7.2 Connectors
7.2.1 Fire Relay Connector
(J2) Fire Relay
Description
Pin 1 & Pin 2 (Left Most)
Normally Open Side of Relay
Pin 3 & Pin 4 (Middle)
Common or Center Side of Relay
Pin 5 & Pin 6 (Right Most)
Normally Closed Side of Relay
7.2.2 Verify and Aux. Connector
(J3) Verify/Aux.
Description
Pin 1 & Pin 2 (Left Most)
Verify Relay Common Side of Relay
Pin 3 & Pin 4
Verify Relay NO or NC Side of Relay
Pin 5
Aux. Relay Common Side of Relay
Pin 6 (Right Most)
Aux. Relay NO or NC Side of Relay
7.2.3 Fault Connector
(J4) Fault Relay
Description
(Normally Energized
State)
Pin 1 (Left Most)
Normally Closed Side of Relay
Pin 2 (Middle)
Common Side of Relay
Pin 3 (Right Most)
Normally Open Side of Relay
7.2.4 RED1 - Power/Communications Connector
(J5) Power/Communications
Description
Pin 1 & Pin 5 (Left Most)
Power (DC -)
Pin 2 & Pin 6
Communication RS 485 (-)
Pin 3 & Pin 7
Communication RS 485 (+)
Pin 4 & Pin 8 (Right Most)
Power (DC +)
7.3 Verify/Aux. Relay Configurations
Model #
Verify Relay
Aux. Relay
RED1-HE1
Open Contacts
Closed Contacts
RED1-HE2
Closed Contacts
Open Contacts
RED1-HE3
Open Contacts
Open Contacts
RED1-HE4
Closed Contact
Closed Contacts