Sierra Safety Technology, Inc.
www.sierrasafety.com
All rights reserved - © 2016
Page 4 of 20
detector. “Non-Latching” means that the detector or relay output
will reset when a flame is no longer being sensed by the detector.
SW6 configures the Fire Relay, SW7 configures the Verify Relay,
and SW8 configures the Detector.
The factory defaults are
“Latching” (SW6, SW7, and SW8 are all off).
If the Fire Relay is latching, then the Verify Relay and the Detector
will be latching.
If the Verify Relay is latching, then the Detector will be latching.
2.5.4 High Speed Disable
Switch 9 must be in the
OFF
position to enable the High Speed
response (50 milliseconds).
2.6 LED operation
The status of the RED1 detector can be determined from the LEDs on
the front of the detector. The LEDs indicate the detectors status (Power
Up, Fault Mode, Normal Mode Fire Mode or Verified Fire Mode).
2.6.1 Power Up
On power up the LEDs will display the Switch Configuration. They
will flash 9 times with the first flash being switch 1 and the last
flash being switch 9. If one LED flashes then the switch is in the
off position. If two LEDs flash, then the switch is in the on
position. Note that switch 7 overrides switch 8 and switch 6
overrides switch 7 (see Latching)
2.6.2 Normal Mode
In Normal Mode the LEDs will flash briefly every 8 seconds.
Whenever the device is in any other mode the “flash every 8
seconds” is suspended until the detector returns to Normal Mode.
2.6.3 Fire Mode
When the RED1 declares a fire both LEDs will come “on”. If the
detector is set to “Latching” the LEDs will remain “on” and stay
“on” until the detector is powered down. If the Fire Relay is set to
“Non-Latching” then the Relay will reset when the fire has not
been detected for a period of time (factory default is 3 seconds).
2.6.4 Verify Mode
When a verified fire is declared the LEDs will blink “off” briefly
every second. If the Verify Relay is set to “Non-Latching” then
the Relay will reset when a verified fire has not been detected for
a period of time (factory default is 3 seconds).
2.6.5 Fault Mode
If the detector has power and is showing a fault then LED1 (the
LED on the left, when facing the detector, with the configuration
switches below the LEDs) will turn “on for 5 seconds and the
LED2 (the right LED) will be “off”. Then LED1 will turn “off” and