Operation

The 

SIEMENS

 System 3 Intrinsically Safe Zone Model

ZS-30, consisting of a Zone Module and a Diode

Shunt Barrier, is designed for use in System 3 low

voltage control panels. With detection devices located

in hazardous areas identified as Class I, II, and III,

Division 1, Groups A, B, C, D, E, F, and G, the intrinsi-

cally safe characteristic is achieved by using a diode

shunt barrier (P/N 515-180238) with the ZS-30. The

Diode Shunt Barrier, though physically a separate unit

of ZS-30, must always be used to achieve an intrinsi-

cally safe zone. The Diode Shunt Barrier limits the

energy to the detector circuit.
The following equipment is covered by this instruction

sheet.

     Item Name and

     Model Number

                

Description

 NON-HAZARDOUS   LOCATION EQUIPMENT

Model ZS-30

Zone module (P/N 515-022079)

Model 515-180238

Diode shunt safety barrier

(P/N 515-180238)

 HAZARDOUS LOCATION EQUIPMENT

Detector DI-3IS

Detector S121

Detector S122

Base DB-3

For use with DI-3IS

Cable 465-514391

Limited-energy shielded cable

(Optional)

Check that each device to be located in the intrinsi-

cally safe area has an FM intrinsically safe label. In

addition, direct shorting manual stations and/or

thermal detectors (devices not containing any energy

storing, or voltage producing, components) may be

connected in the detector loop without jeopardizing the

intrinsically safe characteristics of the system.

NEC Hazardous Location Classification

Class I: 

Class I locations are those in which flammable

gases or vapors are (or may be) present in the air in

quantities sufficient to produce explosive or ignitable

mixtures.

Class II:

 Class II locations are those that are hazardous

because of the presence of combustible dust.

Class Ill:

 Class Ill locations are those that are hazardous

because of the presence of easily ignitable fibers or

flyings, but in which such fibers or flyings are not likely

to be in suspension in the air in quantities sufficient to

produce ignitable mixtures.

Division 1:

 A Division 1 location is a location (a)

 

in

which hazardous concentrations of flammable gases or

vapors exist continuously, intermittently, or periodically

under normal operating conditions; or (b) hazardous

concentrations of such gases or vapors may exist

frequently because of repair or maintenance operations

or because of leakage; or (c) breakdown or faulty

operation of equipment or processes that might release

hazardous concentrations of flammable gases or vapors

occur and might also cause simultaneous failure of

electric equipment.

Group A:

Group A atmospheres contain acetylene.

Group B:

Group B atmospheres contain such chemi-

cals as butadiene, hydrogen ethylene oxide

(or gases or vapors of equivalent hazard to

hydrogen, such as manufactured gas), or

propylene oxide.

Group C:

Group C atmospheres contain such chemicals

as acetaldehyde, cyclopropane, diethyl

ether, ethylene, isoprene, or unsymmetrical

dimethyl hydrazine (UDMH).

Group D:

Group D atmospheres contain such chemicals

as acetone, acrylonitrile, alcohols, ammonia,

Operation and Installation Instructions

MODEL ZS-30

Intrinsically Safe Module

Fire Safety

Siemens Building Technologies, Inc.

8 Fernwood Road

Florham Park, New Jersey 07932

Siemens Building Technologies, Ltd.

2 Kenview Boulevard

Brampton, Ontario L6T 5E4 CN

P/N 315-024056-17

Содержание ZS-30

Страница 1: ...ties sufficient to produce explosive or ignitable mixtures Class II Class II locations are those that are hazardous because of the presence of combustible dust Class Ill Class Ill locations are those that are hazardous because of the presence of easily ignitable fibers or flyings but in which such fibers or flyings are not likely to be in suspension in the air in quantities sufficient to produce i...

Страница 2: ...he barrier and detector circuit The module is mounted on a System 3 panel along with the control unit The intrinsically safe module is interconnected to System 3 modules bus wire cable and draws its power from the System 3 power supply through the control unit The module provides regulated voltage to the detectors in the hazardous locations through the Diode Shunt Barrier It also detects and gener...

Страница 3: ...re or in its own enclosure Proper assembly and conduit are essential follow Figure 1 Non energy storing devices such as a manual station may be connected in the detector loop without jeopar Figure 2 Barrier Label dizing the intrinsically safe characteristics of the system Such devices must be connected in parallel with the barrier output must not contain any energy storing component s and must be ...

Страница 4: ...S CAN BE USED IN ADDITION TO MECHANICAL NON ENERGY STORING SHORTING DEVICES 5 MAXIMUM SAFE SYSTEM VOLTAGE IS 250 VAC Figure 3 Wiring Diagram ZS 30 Intrinsically Safe Zone P N 315 024056 17 6 REFER TO TEXT FOR LIMITATIONS AND DEFINITION OF THE HAZARDOUS AREA 7 ONLY MECHANICAL NON ENERGY STORING SHORTING DEVICES SUCH AS THE MS 51 MANUAL STATION MAY BE USED 8 WARNING DO NOT MAKE ANY CONNECTION TO TER...

Отзывы: