Consecutive number of
the captured networks
Network ID
Display of the radio signal strength
During the scanning process the radio signal strength of the net
-
works is updated continuously. For example, while the display loop
is running, a node with a better signal strength may have been found
for a network already displayed with a certain signal strength. This
network is shown with the better signal strength the next time it is
displayed.
The network scan is ended after 4 minutes. All captured networks are shown consecutively in the display (1), each for 3 sec
-
onds.
Short press the red button (2) to page forward display levels manually
.
Example:
3 sec
3 sec
3 sec
3 sec
At the same time the gateway sets up a link to the S GCP and transmits the results of the network scan to the S GCP for
validity checking. The result of the check is returned to the gateway.
Successful auto install
Auto install is successful if the gateway has received all required networks defined in the S GCP.
If the conditions of the check are fulfilled, the buzzer generates a short tone, the
LED (3) flashes green and the "INSTALL
" + "OK" message appears in the
display (1).
The gateway can now be mounted on the wall.
The "
INSTALL
" + "OK
" message is shown in the display for 60 minutes. The gateway is then placed in sleep mode. The
gate-
way can also be placed in sleep mode manually by a long press of the red button (2)
.
Failed auto install
Auto install has failed if the gateway has not received the required networks defined in the S GCP.
If automatic installation of the WTT563.. has failed,
the buzzer generates a short tone, the LED (3)
flashes red and the
"
FAILED" message is shown in the Display (1) for 60 minutes. The gateway is then
placed in sleep mode. The gateway can also be placed in sleep mode manually with a long press of the
red button (2).
Reasons for failure of the installation can be
poor radio reception or the
conditions of the validity check in the S GCP
were not
fulfilled.
In this case we recommend the following procedure:
•
Change the position within the building to achieve better radio conditions and restart the auto install.
•
Contact the technical customer service department or your supplier to have the configuration of the gateway checked and
corrected.
Evaluation of the signal strength
GSM signal strength
Radio signal strength, network nodes
Symbol
Evaluation
A2
A1
A0
All A0 + A1 + A2 segments switched on
very good
All A0 + A1 segments switched on
good
A0 segment only switched on
weak
Symbol
Evaluation
5 segments
Excellent
4 segments
very good
3 segments
good
2 segments
adequate
1 segment
Too low
Status messages
No other action can be started while the gateway is performing an operation.
If the user attempts to start an action by pressing a button while the device is still performing an
operation, the buzzer generates a short tone, the LED (3) flashes red and the "busy" message is shown
in the display (1).