APOGEE Wireless User Guide
Chapter 5–Modifying the WRS/RSX Pair
This chapter provides information on changing WRS/RSX pair settings and devices.
Replacing WRS Battery
The battery within the WRS should be replaced when its voltage drops below 3.2 Vdc.
When the battery drops below 3.2 Vdc, the following occurs:
•
The Battery icon (
)
fl
ashes on an WRS with an LCD.
•
The WRS reports a low battery condition to the RSX, which then commands bit 3 (with the least
signi
fi
cant bit of bit 0) in the ERROR STATUS point 99 in the TEC to 1. At the workstation, an alarm
can be set up to report WRS low battery condition using the value of TEC point 99.
You can also check battery status using the
STATUS WRS
command at the WRS. You should replace
the battery when:
•
LOW BATTERY is set to YES.
•
BATTERY STATUS (VOLTS) value is below 3.2.
To replace the battery, remove WRS from the base plate and install new battery. See
Wireless Room
Sensor Installation Instructions
for details on mounting/unmounting the WRS from the base plate.