background image

GAMMA 

instabus

 

Technical Product Information 

February 2010 

Blind actuator UP 520/31 

5WG1 520-2AB31 

 

Technical Manual 

UP 520/31, 4 pages 

Siemens AG  

 

 

Industry Sector, Building Technologies 

Update: http://www.siemens.com/gamma 

© Siemens AG 2010 

Low Voltage Distribution

                         

 

Subject to change without further notice 

PO Box 10 09 53, D-93009 Regensburg 

2.10.1.18/2 

Technical specifications 

 

Power supply 

 

Carried out via the bus line 

 

Power consumption: typically 150 mW 

 

Outputs 

 

Number: 1 output, potential-free relay contact (µ-contact)  

 

Rating voltage: AC 230V,  

 

Switching power: max. 1 motor 1000 VA 

 

Switching behavior:   Can be parameter set, depending   

    on function 
 

Contacts 

 

Output: Contact the load on H07V-K 1,5 mm

2

 with the 

attached clamps. 

  Inputs and bus line: Line  YY 6x0.6 mm

 

Approx. 33cm pre-assembled, can be laid to max. 5m 

 

Mechanical specifications 

 

Casing: plastic 

 

Dimensions: d =53mm, height = 28 mm 

 

Weight: approx. 88g 

 

Mounting: in box mounts, Ø 60mm, depth: 40mm 

 

Electrical safety 

 

Degree of pollution (to IEC 60664-1): 2 

 

Protection class (to EN 60529): IP 20 

 

Protection class (to IEC 61140): III 

 

Overvoltage category class (to IEC 60664-1): III 

 

Bus: safety extra low voltage SELV DC 24V 

 

Device complies with EN 50090-2-2 and IEC 60664-1 

 

Reliability 

Failure rate: 170 fit at 40°C 

 
EMC criteria 

 

Complies with EN 61000-6-2, EN 61000-6-3 and EN 
50090-2-2 

 

Environmental specifications 

 

Climatic conditions: EN 50090-2-2 

 

Ambient temperature in operation: - 5 ... + 45 

°

 

Storage temperature: - 25 ... + 70 

°

(Storage above + 45°C reduces the service life) 

 

Relative humidity (non-condensing): 5% to 93% 

 

Markings 

 

KNX  

EIB

 

 

CE mark 

 

to EMC directive (residential and functional building)  

Location and functioning of the display and 
operating elements  

 
 

PK

BK

EIB+ / RD
EIB-  / BK
A       / GN
com  / WH

B       / YE
com  / BN

Prog.

U  230V

n

 

 

Figure 1: Location of the indicating and operating elements 

 
X  Connector cables low voltages 

Red:  

Bus  (+) 

Black: Bus 

(-) 

Green: input 

White: 

Reference potential (com) 

Yellow: Input 

Brown: 

Reference potential (com) 

Y  Connector cables load 
 

black:  L    //  brown:  Up    //  pink:  Down   

Program button / -LED (red) 

 

Содержание UP 520/31

Страница 1: ... operation see state of delivery or alternatively also as binary inputs on the Instabus The connected potential free switch or push button contacts are read in via a common reference potential on the actuator As binary input telegrams can be transmitted for switching or dimming for Venetian blind control value setting or scene recall save State of delivery When delivered the switching state of the...

Страница 2: ... in box mounts Ø 60mm depth 40mm Electrical safety Degree of pollution to IEC 60664 1 2 Protection class to EN 60529 IP 20 Protection class to IEC 61140 III Overvoltage category class to IEC 60664 1 III Bus safety extra low voltage SELV DC 24V Device complies with EN 50090 2 2 and IEC 60664 1 Reliability Failure rate 170 fit at 40 C EMC criteria Complies with EN 61000 6 2 EN 61000 6 3 and EN 50090...

Страница 3: ...ective country are to be considered During installation ensure adequate insulation between mains voltage and bus or extensions A minimum spacing should be maintained between bus extension cable cores and mains voltage cable cores of at least 4 mm cf figure 3 Æ Inputs Two extension inputs can be used for the connection of potential free contacts for local control or as binary inputs cf figure 4 Lin...

Страница 4: ...nes have to connect by using the attached clamps Do not connect three phase AC motors to blind actuators Observe the instructions of the motor manufacturers if motors are to be connected in parallel Otherwise risk of irreparable damage to the motors Use only blinds or shutters with limit switches mechanical or electronic The limit switches of the connected motors must be checked for correct adjust...