Technical specifications
Power supply
•
Carried out via the bus line
•
Power consumption: typically 150 mW
Outputs
•
Number: 1 output, potential-free relay contact (µ-contact)
•
Rating voltage: AC 230V,
•
Switching power: max. 1 motor 1000 VA
•
Switching behavior: Can be parameter set, depending
on function
Contacts
•
Output: Contact the load on H07V-K 1,5 mm
2
with the
attached clamps.
•
Inputs and bus line: Line YY 6x0.6 mm
Approx. 33cm pre-assembled, can be laid to max. 5m
Mechanical specifications
•
Casing: plastic
•
Dimensions: d =53mm, height = 28 mm
•
Weight: approx. 88g
•
Mounting: in box mounts, Ø 60mm, depth: 40mm
Electrical safety
•
Degree of pollution (to IEC 60664-1): 2
•
Protection class (to EN 60529): IP 20
•
Protection class (to IEC 61140): III
•
Overvoltage category class (to IEC 60664-1): III
•
Bus: safety extra low voltage SELV DC 24V
•
Device complies with EN 50090-2-2 and IEC 60664-1
Reliability
Failure rate: 170 fit at 40°C
EMC criteria
•
Complies with EN 61000-6-2, EN 61000-6-3 and EN
50090-2-2
Environmental specifications
•
Climatic conditions: EN 50090-2-2
•
Ambient temperature in operation: - 5 ... + 45
°
C
•
Storage temperature: - 25 ... + 70
°
C
(Storage above + 45°C reduces the service life)
•
Relative humidity (non-condensing): 5% to 93%
Markings
•
KNX
EIB
CE mark
•
to EMC directive (residential and functional building)
Location and functioning of the display and
operating elements
PK
BK
EIB+ / RD
EIB- / BK
A / GN
com / WH
B / YE
com / BN
Prog.
U 230V
n
~
Figure 1: Location of the indicating and operating elements
X Connector cables low voltages
Red:
Bus (+)
Black: Bus
(-)
Green: input
A
White:
Reference potential (com)
Yellow: Input
B
Brown:
Reference potential (com)
Y Connector cables load
black: L // brown: Up // pink: Down
Z
Program button / -LED (red)