background image

 

GAMMA 

instabus

 

Technical Product Information 

February 2010 

Blind actuator UP 520/31 

5WG1 520-2AB31 

 

Siemens AG 

UP 520/31, 4 pages 

Technical Manual

 

Industry Sector, Building Technologies 
Low Voltage Distribution 

© Siemens AG 2010 Update: 

http://www.siemens.com/gamma 

PO Box 10 09 53, D-93009 Regensburg 

Subject to change without further notice

 

 

 

2.10.1.18/3 

Mounting and wiring 

 

Æ

 General: 

It is recommended that the actuator is installed in two 
flush sockets connected to one another (cf. fig. 2). One 
socket (A) can accommodate, e.g., a series switch (C) as 
well as the bus and extension connection. The other 
socket (B) accommodates the    actuator and the 230 V 
terminals. The 6-pole connection lead (D) is guided 
through the socket connection. 
 

A

23

0 V

B

C

D

 

 

Figure 2 

 

230 V

Bus/Com/A,B

> 4 mm

 

 

Figure 3 

 

V

 

Danger

 

 

The device must be mounted and commissioned 
by an authorized electrician. 

 

When connecting the device, it should be 
ensured that the device can be isolated. 

 

The device must not be opened. 

 

For planning and construction of electric 
installations, the relevant guidelines, regulations 
and standards of the respective country are to be 
considered. 

 

During installation, ensure adequate insulation 
between mains voltage and bus or extensions! A 
minimum spacing should be maintained 
between bus / extension cable cores and mains 
voltage cable cores of at least 4 mm.  
(cf. figure 3) 

 

Æ

 Inputs: 

Two extension inputs can be used for the connection of 
potential-free contacts for local control or as binary inputs. 
(cf. figure 4) 
Line  YY 6x 0.6 mm

 

Approx. 33cm pre-assembled, can be laid to max. 5m 
 

COM

COM

A

B

U      = - 19 V (ca./approx.)

com

U

COM

U

COM

rot / red

schwarz / black
grün / green

weiß / white
gelb / yellow

braun / brown

 KNX

A

B

(-)

(+)

 

Figure 4 

 

 

Caution

 

 

To avoid disruptive EMI irradiation, the lines of the 
inputs should not be laid parallel to lines conducting 
mains voltage. 

 

Input A (green), input B (yellow) and reference 
potential (com) (white and brown) must not 
connect to inputs or reference potential (com) of 
other devices. 

 

V

 

Danger

 

 

On no account should you connect mains voltage 
(230 V) or other external voltages to the extension 
inputs! Connection to an external voltage would 
endanger the electrical safety of the entire KNX/EIB 
system (SELV / no galvanic isolation)! 
 
People can be at risk, equipment and devices can be 
destroyed! 

 

Unused cable cores of the 6-pole connection lead 
are to be insulated from one another and from 
external voltages. 

 

 

Содержание UP 520/31

Страница 1: ... operation see state of delivery or alternatively also as binary inputs on the Instabus The connected potential free switch or push button contacts are read in via a common reference potential on the actuator As binary input telegrams can be transmitted for switching or dimming for Venetian blind control value setting or scene recall save State of delivery When delivered the switching state of the...

Страница 2: ... in box mounts Ø 60mm depth 40mm Electrical safety Degree of pollution to IEC 60664 1 2 Protection class to EN 60529 IP 20 Protection class to IEC 61140 III Overvoltage category class to IEC 60664 1 III Bus safety extra low voltage SELV DC 24V Device complies with EN 50090 2 2 and IEC 60664 1 Reliability Failure rate 170 fit at 40 C EMC criteria Complies with EN 61000 6 2 EN 61000 6 3 and EN 50090...

Страница 3: ...ective country are to be considered During installation ensure adequate insulation between mains voltage and bus or extensions A minimum spacing should be maintained between bus extension cable cores and mains voltage cable cores of at least 4 mm cf figure 3 Æ Inputs Two extension inputs can be used for the connection of potential free contacts for local control or as binary inputs cf figure 4 Lin...

Страница 4: ...nes have to connect by using the attached clamps Do not connect three phase AC motors to blind actuators Observe the instructions of the motor manufacturers if motors are to be connected in parallel Otherwise risk of irreparable damage to the motors Use only blinds or shutters with limit switches mechanical or electronic The limit switches of the connected motors must be checked for correct adjust...

Отзывы: