background image

GAMMA

instabus

Technical – Product Information

February 2014

Temperature Controller

UP 237K

5WG1 237-2KB_1

UP 254K

5WG1 254-2KB_3

Siemens AG

UP 237K, UP 254K, 5 pages

Technical-Manual

Infrastructure & Cities Sector, Building Technologies
Control Products and Systems

ã

 Siemens AG 2014

Update: http://www.siemens.com/gamma

P. O. Box 10 09 53, D-93009 Regensburg

Subject to change without further notice.

2.8.2.8/3

Mechanical data

·

  Casing: plastic

·

 Dimensions:

-

Temperature controller UP 237K for DELTA i-
system
(L x W x D): 55 x 55 x 16 mm (without spring)

-

Temperature controller UP 254K for DELTA style
(L x W x D): 68 x 68 x 20 mm (without spring)

·

  Weight: approx. 30 g (UP 237K)

·

  Weight: approx. 40 g (UP 254K)

·

  Fire load: 730 KJ

±

 10 %

·

 Mounting: The operator panel is attached to the BTM

UP 117 and screwed to its mounting frame.

Electrical safety

·

  Degree of pollution (according to IEC 60664-1): 2

·

  Type of protection (according to EN 60529): IP 20

·

  Protection class (according to IEC 61140): III

·

  Overvoltage categorie (according to IEC 60664-1): III

·

  Bus: Safety extra-low voltage SELV DC 24V

·

  Device complies with EN 50090-2-2

Reliability

·

  Failure rate: 214  fit at 40°C

EMV requirements

·

  Complies with EN 61000-6-1 and 50090-2-2

Environmental conditions

·

  Climatic withstand capability: EN 50090-2-2

·

  Ambient operating temperature: - 5 ... + 45

°

C

·

  Storage temperature: - 25 ... + 70

°

C

·

  Relative humidity (not condensing): 5 % up to 93 %

Markings

·

 KNX

EIB

CE mark

·

  In accordance with the EMV guideline (residential and

functional buildings), low voltage guideline

Location and function of the operating and
display elements

figure 1: Location of the operating and display elements

A1  LED green: illuminates during manual mode
A2  LED green: lights up continuously in comfort mode

and blinks slowly in comfort prolongation.

A3  LED green: illuminates during pre-comfort mode
A4  LED green: illuminates during energy-saving mode
A5  LED green: lights up continuously in protection

mode, blinks slowly in permanent protection mode

A6:  Pushbutton for selection of room operating mode
A7:  LED red: illuminates with dew point alarm
A8:  LED yellow: illuminates if cooling valve is open
A9:  LED red: illuminates if heating valve is open
A10: LED red: illuminates if open window
A11:  Rotary button for manual setpoint shifting (shifting

range dependent on parameter setting) or for set-
point adjustment in °C

Mounting, wiring and commissioning

General description
The temperature controller is attached with the associ-
ated DELTA frame to the BTM UP 117 and screwed to
its mounting frame.

Mounting and commissioning (see figure 2)

-

Attach the bus cable and fix the BTM UP 117 (B8) on
the flush socket (see mounting instructions for BTM
UP 117)

-

Remove rotary knob (B1 or B2) from the temperature
controller (B3)

-

Attach temperature controller with DELTA frame (B4)
to the BTM UP 117  and secure using screw (B5)

-

Press programming button (B7): programming LED
(B6) illuminates

-

Load physical address and the configures application
program by means of the ETS

A1 A2 A3 A4  A5

A6

A7
A8
A9

A10

Содержание UP 237K

Страница 1: ...utton Briefly pressing the button on the control causes switch ing in automatic mode the LED for the display of manual operation is not lit each time between comfort mode and pre comfort mode with four operating modes or between comfort mode and energy savings mode with three operating modes Moreover briefly pressing the button during active energy savings or protection mode starts a comfort prolo...

Страница 2: ...ling ceiling and supply air cooler The following partial functions are part of room tempera ture control Room temperature measurement using the internal temperature sensor with Offset setting Room temperature measurement using an external temperature sensor with Offset setting Computation of current room temperature actual value internal and external sensors weighted With target value shifting Bas...

Страница 3: ...mark In accordance with the EMV guideline residential and functional buildings low voltage guideline Location and function of the operating and display elements figure 1 Location of the operating and display elements A1 LED green illuminates during manual mode A2 LED green lights up continuously in comfort mode and blinks slowly in comfort prolongation A3 LED green illuminates during pre comfort m...

Страница 4: ...h socket Υ WARNING The device must be mounted and commissioned by an authorised electrician The device may not be inserted in the same box as 230 V devices The device may be mounted in switch and socket combinations if VDE certified devices are used exclu sively The prevailing safety rules must be heeded The device may not be opened For planning and construction of electric installations the relev...

Страница 5: ...8 5 Dismantling see figure 2 Remove rotary knob B1 or B2 Loosen screw B5 Remove controller together with DELTA frame Remove BTM UP 117 B8 according to dismantling in structions Dimension Drawing DELTA i system temperature controller UP 237K Dimensions in mm 55 55 16 DELTA style temperature controller UP 254K Dimensions in mm 68 68 20 General Notes The operating instructions must be handed over to ...

Отзывы: