Technical Product-Information

February 2014

Temperature Controller

UP 237K

5WG1 237-2KB_1

UP 254K

5WG1 254-2KB_3

Technical-Manual

UP 237K, UP 254K, 5 pages

Siemens AG

Infrastructure & Cities Sector, Building Technologies

Update: http://www.siemens.com/gamma

ã

 Siemens AG 2014

Control Products and Systems

Subject to change without further notice.

P. O. Box 10 09 53, D-93009 Regensburg

2.8.2.8/4

-  Replace rotary knob (B1 or B2).

figure 2: Mounting controller

B1  Rotary button for setpoint shifting
B2  Rotary button for setpoint adjustment in °C
B3  Temperature controller heating / cooling
B4  DELTA frame
B5  Screw for securing the controller to the mounting

frame of the UP 117 (anti-theft protection)

B6  LED for displaying normal mode (LED Off) or ad-

dress mode (LED On); it is automatically extin-
guished once the physical address has been trans-
ferred

B7 

Button  for  toggling  between  normal
mode/addressing mode for transferring the physical
address

B8  Bus Transceiver Module UP 117

Installation instructions

·

 The device can be used for fixed installations, in dry

interior spaces and for integration into a flush socket.

Υ

WARNING

·

  The device must be mounted and commissioned by an

authorised electrician.

·

 The device may not be inserted in the same box as

230 V devices.

·

  The device may be mounted in switch and socket

combinations if VDE-certified devices are used exclu-
sively.

·

  The prevailing safety rules must be heeded.

·

  The device may not be opened.

·

  For planning and construction of electric installations,

the relevant guidelines, regulations and standards of
the respective country are to be considered.

Mounting location (see figure 3)
Observe the following points when mounting the control-
ler:

Controller mounted on interior wall of room to be condi-
tioned, vis-á-vis the heat source:

·

  At ca. 1.5 m height in the room and at least 50 cm

  from the next wall.

·

  Not on outside walls.

·

  Not in niches or behind curtains.

·

  Not above or near heat sources or shelves.

·

  Not on walls covering heat sources such as a chim-

 ney.

·

 Not in the radiation range of heat sources and lighting

   bodies e.g. spotlights.

·

  Not in areas exposed to direct solar radiation.

The air draft of windows and doors have to be avoided!

figure 3: Installation references for sensors and tempera-
              ture controller.

Seal the end of the installation conduit to prevent false
measurements due to air drafts, see figure 4.

figure 4: Sealing installation conduit

B1

B2

B3

B4

B5

B6

B7

B8

Содержание UP 237K

Страница 1: ...utton Briefly pressing the button on the control causes switch ing in automatic mode the LED for the display of manual operation is not lit each time between comfort mode and pre comfort mode with four operating modes or between comfort mode and energy savings mode with three operating modes Moreover briefly pressing the button during active energy savings or protection mode starts a comfort prolo...

Страница 2: ...ling ceiling and supply air cooler The following partial functions are part of room tempera ture control Room temperature measurement using the internal temperature sensor with Offset setting Room temperature measurement using an external temperature sensor with Offset setting Computation of current room temperature actual value internal and external sensors weighted With target value shifting Bas...

Страница 3: ...mark In accordance with the EMV guideline residential and functional buildings low voltage guideline Location and function of the operating and display elements figure 1 Location of the operating and display elements A1 LED green illuminates during manual mode A2 LED green lights up continuously in comfort mode and blinks slowly in comfort prolongation A3 LED green illuminates during pre comfort m...

Страница 4: ...h socket Υ WARNING The device must be mounted and commissioned by an authorised electrician The device may not be inserted in the same box as 230 V devices The device may be mounted in switch and socket combinations if VDE certified devices are used exclu sively The prevailing safety rules must be heeded The device may not be opened For planning and construction of electric installations the relev...

Страница 5: ...8 5 Dismantling see figure 2 Remove rotary knob B1 or B2 Loosen screw B5 Remove controller together with DELTA frame Remove BTM UP 117 B8 according to dismantling in structions Dimension Drawing DELTA i system temperature controller UP 237K Dimensions in mm 55 55 16 DELTA style temperature controller UP 254K Dimensions in mm 68 68 20 General Notes The operating instructions must be handed over to ...

Отзывы: