9
Siemens
A6V12681516_enUS_a
Smart Infrastructure
10/12/2022
Technical data
Power supply
Operating voltage
AC 24 V (± 15 %) or DC 24 V (± 20 %)
Frequency
50/60 Hz
Power consumption
3 VA (AC); 1.2 W (DC)
Primary fuse or breaker rating
External, 2 A quick blow
Signal input
Control signal
DC 0…10 V
Input impedance
100 kOhm
Parallel operation (number of actuators)
Max. 10
1)
1)
Provided that the controller output is sufficient.
Operating data
Position with de-energized contact Y
Running speed (time for 5.5 mm)
< 5 s/mm ± 25 % (27.5 s ± 25 %)
Positioning force
45 lbf (200 N)
Stroke
0.05 to 0.25 inch (1.2…6.5 mm)
Permissible temperature of medium in the connected valve
34 to 248°F (1…120
℃
)
Electrical connection
Permissible length for signal lines
65 ft (20 m)
Wire cross section
18...20 AWG (0.5...0.75 mm²
)
Cable diameter
<0.2 inch (5 mm)
Mounting
Connection to valve
Plastic coupling nut 3/4” inch
Orientation
Above horizontal
Standards
EU conformity (CE)
A5W00254962A
RCM conformity
A5W00254983A
UKCA
A5W00257055A
Housing protection degree
NEMA 2 / IP20 (EN 60529)
Protection class according to EN 60730
III
Pollution degree
2
Содержание SSB161.05U