background image

6/8 

Siemens Building Technologies 

Electric actuators for butterfly valves 

CM1N4506en 

HVAC Products 

 

07.06.2004 

The angle of rotation is factory-set to 90°. However, the angle can be changed to 
between 70° and 180°. This may be necessary when using non-Siemens valves. 
Special notes on this subject will be found in the mounting instructions for the ASK40 
and ASK41 (mounting kits for non-Siemens valves). 
 

Maintenance 

The actuators require no maintenance. 
When servicing the valve and/or actuator: switch OFF the pump and power 
supply, close the main shut-off valve in the pipework, release pressure in the 
pipes and allow them to cool down completely.  
If necessary, disconnect electrical connections from terminals.  

 

Disposal 

 

The device may not be disposed of together with domestic waste.

 

This applies in 

particular to the PCB. 
Legislation may demand special handling of certain components, or it may be sensible 
from an ecological point of view. 

Current local legislation must be observed.

 

 

Warranty 

The technical data given for these applications is valid only in conjunction with the 
Siemens valves (butterfly and slipper valves) and third-party valves for use with the 
ASK40 / ASK41, as described under "Compatibility".  The use of third-party valves 
other than those recommended by Siemens invalidates the warranty.  
 

Technical data 

 

Power supply 

Rated voltage 
   SQK33.00, SQL33.00, SQL33.03 
   SQL83.00 

 
AC 230 V ± 15 % 
AC 24 V ± 20 % 

 

Rated frequency 

50 / 60 Hz 

 Control 

signal 

3-position 

 Power 

consumption 

*) 

   SQK33.00 
   SQL33.00, SQL83.00 
   SQL33.0... 

 
3 VA 
4 VA 
6.5 VA 

 

 

 

 

Operating data 

Run-time for rotation through 90° 

at 50 Hz 

at  60 Hz 

 

   SQK33.00, SQL33.00 
   SQL83.00 
   SQL33.03 

125 s 
125 s

 

30 s 

105 s 
105 s

 

25 s

 

 Angle 

of 

rotation 

   Factory setting 
   Adjustment range 

 
90° ± 2° 
70° ...180°  

 
 
 

Setting the angle of  
rotation 

.

Warning ! 

.
.
.
.
.
.
.
.
.
.

Содержание SQU83

Страница 1: ... potentiometer for additional functions Nominal angle of rotation 90 Reversible electric motor For mounting on butterfly valves and slipper valves with ASK mounting kit With manual adjuster and position indicator Use For use in heating ventilation and air conditioning systems to operate Siemens butterfly valves and three port and four port slipper valves mixing valves types K1i VKF41 VB and VC see...

Страница 2: ...n voltage signal for 90 at 50 Hz accessories SQK33 00 AC 230 V 3 position 125 s 1 x ASC9 5 only 1 auxiliary switch SQL33 00 AC 230 V 125 s 1 x ASC9 5 or 1 auxiliary switch SQL33 03 AC 230 V 3 position 30 s 1 x ASC9 4 or 1 dual auxiliary switch SQL83 00 AC 24 V 125 s 1 x ASZ7 4 1 auxiliary switch and 1000 Ω potentiometer ASK31 For slipper valves type VBF21 DN65 DN150 Series 01 ASK32 For slipper val...

Страница 3: ...40 200 40 200 ASK33 Mounting kits ASK40 and ASK41 for non Siemens actuators refer to data sheet N42291 Mechanical design The electric actuators require no maintenance They have a reversible synchronous motor and reduction gears with self lubricating sinter bearings The housing base and the console are die cast aluminium and the cover is plastic AUTO and MANUAL modes can be selected with a rotary s...

Страница 4: ...ngineering Butterfly valves see data sheets N4100 N4199 Three port and four port slipper valves see data sheets N4200 N4299 Admissible ambient temperatures see Technical data The actuators must be electrically connected in accordance with local regulations and with the connection diagrams Regulations and requirements to ensure the safety of people and property must be observed at all times If addi...

Страница 5: ... and test the functions This also applies to any additional components fitted e g auxiliary switch or potentiometer Siemens slipper valves up to DN50 can be commissioned without an actuator being fitted In this case the flow rate must be adjusted manually with the standard manual adjuster fitted to the valve For automatic operation the rotary switch must be set to AUTO AUTO Automatic operation MAN...

Страница 6: ...is applies in particular to the PCB Legislation may demand special handling of certain components or it may be sensible from an ecological point of view Current local legislation must be observed Warranty The technical data given for these applications is valid only in conjunction with the Siemens valves butterfly and slipper valves and third party valves for use with the ASK40 ASK41 as described ...

Страница 7: ...ty To IEC 721 3 3 Class 3K5 15 55 C 5 95 rh Transport Environmental conditions Temperature Humidity To IEC 721 2 3 Class 3K2 30 65 C 95 rh Storage Environmental conditions Temperature Humidity To IEC 721 1 3 Class 3K1 15 55 C 0 95 rh Industry standards Meets the requirements for CE marking in EMC Directive Low Voltage Directive 89 336 EEC 73 23 EEC Housing protection standard IP44 to IEC529 DIN400...

Страница 8: ...allation height H for actuator with mounting kit ASK31 162 mm ASK32 132 mm ASK33 162 mm Installation height H for actuator with mounting kit ASK31 188 mm ASK32 158 mm ASK33 188 mm Installation height of slipper or butterfly valve from the middle of the pipe Installation height H of the actuator with mounting kit Minimum clearance from ceiling or wall for mounting connection operation service etc 1...

Отзывы: