Engineer Programming Via the Keypad
55
Siemens Building Technologies
Fire Safety & Security Products
09.2008
Timer Description
*Default
EXTERNAL BELL TIME
Duration that external sounders will sound when alarm is activated
(Note: minimum bell time is 90 seconds)
15
INTERNAL BELL TIME
Duration that Internal sounders will sound when alarm is Activated
15
EXTERNAL BELL DELAY
Causes a delayed activation of the external bell
0
STROBE TIME
Duration that the strobe output is active when an alarm is Activated
15
CHIME TIME
Number of seconds that a chime output will activate, when a zone with
CHIME attribute opens
2
DIALLER DELAY
The dialler delay initiates a pre-defined delay period (0 -30 seconds)
before the system dials out to an Alarm Receiving Centre. This is
specifically designed to reduce unwarranted responses from Alarm
Receiving Centres and the constabulary. In the event of a subsequent
zone being tripped, the dialler delay period is ignored and the dialler
dials out immediately.
30
SOAK DAYS
The number of days a zone remains under soak test before it
automatically returns to normal operation
14 Days
DOUBLE KNOCK
The maximum delay between activations of zones with the double
attribute, which causes an alarm
10 Seconds
MAINS SIGNAL DELAY
The time after a Mains fault has been detected before an alert is
activated by the system
0 Minutes
KEYPAD TIMEOUT
The number of seconds that an RKD will wait for key entry before it
leaves the current menu
30 Seconds
WIRELESS FAILED TO SET
(FTS)*
The number of minutes without supervision that will prevent arming
*Wireless features and devices will be available with a later market
package.
0 Minutes
WIRELESS LOST*
The number of minutes without a supervision signal being received by
the SPC Controller before it reports the sensor as being lost
*
Wireless features and devices will be available with a later market
package.
720 Minutes
ENGINEER ACCESS TIME
The time period engineer access is permitted; this timer starts as soon
as the user selects ALLOW ENGINEER in the GRANT ACCESS user
menu option
0 Minutes
ENTRY TIME
The time period allowed for the user to UNSET the alarm, having
opened an entry/exit zone of an armed system
45 Seconds
EXIT TIME
The time period allowed for the user to exit the building after having set
the system
45 Seconds
BELL ON FULLSET
Activates the external bell momentarily to indicate a full set condition
0 Seconds
STROBE ON FULLSET
Activates the strobe on the external bell momentarily to indicate a full
set condition
0 Seconds
FINAL EXIT TIME
The number of seconds arming is delayed after a zone programmed
with the final exit attribute is closed
7 Seconds
TECH DELAY
The number of seconds before attributes for tech zones are activated
0 Seconds
FAIL TO SET
The number of seconds before the system notifies user of a Fail to Set
status following attempt to set alarm
10 Seconds
Tab. 9
Timers
NOTE
Default times are dependent upon the Engineer configuration.
* The default times denoted may or may not be allowable and is dependent on the configuration by the