5.3 Connecting up
SIWAREX WL200
26
Operating Instructions, 07/2016, A5E02199611B-03
Procedure
Note
Measurement errors
Observe the warnings concerning extending or shortening the connecting cables in section
→
Lengthening and shortening the connecting cable (Page 31).
If at all possible, do not shorten the connecting cables in a four-wire system.
Note
No calibration approval
In scales requiring official calibration, the connecting cables for load cells in a four-wire
system must not be shortened or lengthened.
1.
Connect the recommended grounding cables: →
2.
Connect the load cells in accordance with the connection principle and with reference to
the specified signal as
signments: →
Connecting principle (Page 22)
3.
For load cells with a four-wire system, position the wire jumpers in the junction box as
follows:
Table 5- 2
Wire jumpers for load cells with four-wire system
Wire jumper
From terminal
To terminal
1
EXC-
SENSE-
2
EXC+
SENSE+
Note
Malfunction
If the wire jumpers are missing, the SIWAREX weighing module signals a wire break.
Содержание SIWAREX WL200 Series
Страница 6: ...Table of contents SIWAREX WL200 6 Operating Instructions 07 2016 A5E02199611B 03 ...
Страница 12: ...Safety instructions 2 4 Use in hazardous areas SIWAREX WL200 12 Operating Instructions 07 2016 A5E02199611B 03 ...
Страница 20: ...Installing 4 3 Dismantling SIWAREX WL200 20 Operating Instructions 07 2016 A5E02199611B 03 ...
Страница 90: ...Dimension drawings 10 16 SIWAREX WL290 DB S CA SIWAREX WL200 90 Operating Instructions 07 2016 A5E02199611B 03 ...
Страница 100: ...Appendix A 1 Technical support SIWAREX WL200 100 Operating Instructions 07 2016 A5E02199611B 03 ...
Страница 102: ...Index SIWAREX WL200 102 Operating Instructions 07 2016 A5E02199611B 03 W Wheatstone bridge 14 ...