Commissioning
7.6 Manual initialization
SITRANS VP300 with or without HART
Operating Instructions, 03/2011, A5E01258666-03
139
8.
Use to change to the menu "1.2.3 Initialize".
9.
Initialize manually by going through the following six dialog windows.
,QLWLDOL]H
67$57
8SSHUHQGVWRS
,QLWLDOL]H
3OHDVHFRQILUP
/RZHUHQGVWRS
,QLWLDOL]H
3OHDVHZDLW
,QLWLDOL]LQJ
FDQFHO
QH[W!
SUHY
PRYH
QH[W!
PP
!
!
FDQFHO
QH[W!
SUHY
PRYH
QH[W!
PP
!
!
FDQFHO
Figure 7-2
Dialog window for initialization process, using the example of a linear actuator
In dialog window 3/6 (lower endstop), set the relative lower limit up to which the valve is
to close. In dialog window 4/6 (upper endstop), set the relative upper limit up to which the
valve is to open. Hold down or for approx. two to three seconds. The actuator will
begin to move, at first slowly, then with increasingly faster. Move the actuator along with
the value shown in the display in small increments by briefly pressing or a few
times.
Note
The value for the upper endstop must be larger than the value for the lower endstop. If
this is not the case, an error message will be displayed on the display.
Unit depending on setting in %, mm or °.
The progress bar in dialog window 5/6 shows the initialization progress.
Dialog window 6/6 shows that the initialization process has been successfully completed.
10.
Switch to the measurement view by pressing the button until the display shows the
following:
Содержание SITRANS VP300
Страница 2: ......
Страница 130: ...Operate 6 2 Parameter description SITRANS VP300 with or without HART 128 Operating Instructions 03 2011 A5E01258666 03 ...
Страница 184: ...Glossary SITRANS VP300 with or without HART 182 Operating Instructions 03 2011 A5E01258666 03 ...
Страница 188: ...Index SITRANS VP300 with or without HART 186 Operating Instructions 03 2011 A5E01258666 03 ...
Страница 189: ......