Operate
6.2 Parameter description
SITRANS VP300 with or without HART
122
Operating Instructions, 03/2011, A5E01258666-03
Example:
Position
Name of selected trend. In the example graph, parameter "3.7.2.1 Position", i.e.
the trend of the position, has been selected.
x axis
The unit is per the selected trend period
-30 MIN, -8 HOURS, -5 DAYS, -2 MONTHS, -30 MONTHS
In the sample graphic, a trend period of "-30 MIN" has been selected for the
position. This shows the progress of the variable during the last half hour.
y axis
Depending on the selected trend, the values on the y axis mean the following:
Trend
Lower limit
Upper limit
Unit
Position
0
100
%
Deviation of control
-10
10
%
Stiction
0
10
%
Lower endstop
-5
5
%
Upper endstop
-5
5
%
Temperature
-40 (-40)
85 (185)
°C (°F)
Deadband
0
5
%
6.2.3.8
"3.8 Temperature"
This menu is used to enter the current temperatures inside the housing of the field device.
You can also access temperature-related information:
● Actual temperature
● Minimum temperature
● Maximum temperature
● Display of temperature zone histogram
"3.8.1 Current"
Setting range:
Read only
Purpose:
Temperature indicator
Description:
This value indicates the current temperature inside the housing. This
temperature can be measured and displayed in °C or °F depending on
the setting.
If you want to change the unit, change over to parameter:
"3.8.4 Unit" (Page 123)
Содержание SITRANS VP300
Страница 2: ......
Страница 130: ...Operate 6 2 Parameter description SITRANS VP300 with or without HART 128 Operating Instructions 03 2011 A5E01258666 03 ...
Страница 184: ...Glossary SITRANS VP300 with or without HART 182 Operating Instructions 03 2011 A5E01258666 03 ...
Страница 188: ...Index SITRANS VP300 with or without HART 186 Operating Instructions 03 2011 A5E01258666 03 ...
Страница 189: ......