
Operate
6.2 Parameter description
SITRANS VP300 with or without HART
Operating Instructions, 03/2011, A5E01258666-03
99
"3.5.2.1 Start position"
Factory setting:
0.0 %
Setting range:
0.0 ... 100.0
Purpose:
Specifying the start position of the partial stroke test within the range
0.0% to 100.0%. During the test, the actuator moves from this start
position to the target position (start po stroke magnitude).
"3.5.2.2 Start tolerance"
Factory setting:
2.0 %
Setting range:
0.1 ... 10.0
Purpose:
Specifying the start tolerance of the partial stroke test within the range
0.1 to 10.0% relative to the start position.
Description:
Example: You have set 50% as the start position and 2% as the start
tolerance. This means that during operation a partial stroke test is only
initiated between an actual position of 48 and 52%.
"3.5.2.3 Stroke amount"
Factory setting:
10.0 %
Setting range:
0.1 ... 100.0
Purpose:
Specifying the stroke amount by which the actuator is to be moved out
and back, within a range of 0.1 to 100.0%.
"3.5.2.4 Direction of stroke"
Factory setting:
Up
Setting options:
Up
Down
Purpose:
Define the stroke direction for the partial stroke test.
Description:
Up: With Up/Down valves, a valve that is closed by default is
opened by the amount entered in "3.5.2.3 Stroke amount"
Down: With Up/Down valves, a valve that is open by default is
closed by the amount entered in "3.5.2.3 Stroke amount"
Содержание SITRANS VP300
Страница 2: ......
Страница 130: ...Operate 6 2 Parameter description SITRANS VP300 with or without HART 128 Operating Instructions 03 2011 A5E01258666 03 ...
Страница 184: ...Glossary SITRANS VP300 with or without HART 182 Operating Instructions 03 2011 A5E01258666 03 ...
Страница 188: ...Index SITRANS VP300 with or without HART 186 Operating Instructions 03 2011 A5E01258666 03 ...
Страница 189: ......