
Explosion protection
5.1 ATEX
SITRANS SL
76
Operating Instructions, 12/2010, A5E01132948-04
Table 5- 5
Electric connection for PROFIBUS connection cable
Conductor color/no.
Connector position
(Receiver junction board)
Remarks
Function
1 (black)
1
+
Supply voltage
19 ... 30.3 VDC, 10 VA
2 (black)
Chassis
Red
13
A line
Green
14
B line
RS 485
communication
3 (black)
2
-
Supply voltage
19 ... 30.3 VDC, 10 VA
4 (black)
Chassis
Shield wire
15
PROFIBUS shield
Example: Digital out 0
,
PHDV
5
ORDG
&XVWRPHUVLGH
!6,75$166/
9
Figure 5-6
Using digital output
●
V
0
can be maximum 30 V DC.
●
R
load
must be minimum 60 Ω (max. 0.5 A in the relay).
Содержание SITRANS SL
Страница 106: ...Commissioning 6 4 Modbus configuration for SITRANS SL SITRANS SL 108 Operating Instructions 12 2010 A5E01132948 04 ...
Страница 206: ...List of abbreviations SITRANS SL 208 Operating Instructions 12 2010 A5E01132948 04 ...
Страница 212: ...Glossary SITRANS SL 214 Operating Instructions 12 2010 A5E01132948 04 ...