7ML19985QV81
SITRANS Probe LU (PROFIBUS PA) – QUICK START MANUAL
Page A-1
m
mmmm
A: Connect
ion Dr
awi
n
gs
Appendix A: Connection Drawings
FM/CSA Intrinsically Safe Connection Drawing
Note:
Reference drawing 23650617 is available from the product page of our website
at: https://pia.khe.siemens.com/index.asp?Nr=11157.
Product Group
FOR INTERNAL
USE ONLY
S. NGUYEN
PETERBOROUGH
FOR CONSTRUCTION
0
E. DeSIMONE
R. CLYSDALE
1 : 1
1
4
NTS
A
0
RPC
SN
FISCO-Concept
The FISCO Concept allows interconnection of intrinsically safe apparatus to associated apparatus not
specifically examined in such combination. The criteria for interconnection is that the voltage (U or V
), the
current (I , or I
) and the power (P , or P
) which intrinsically safe apparatus can receive and remain
intrinsically safe, considering faults, must be equal or greater than the voltage (U or V
or V ), the current
(l or I
or l ) and the power (P or P
) levels which can be delivered by the associated apparatus,
considering faults and applicable factors. In addition, the maximum unprotected capacitance (C ) and
inductance (L ) of each apparatus (other than the termination) connected to the fieldbus must be less than or
equal to 5 nF and 10 µH respectively.
In each segment only one active device, normally the associated apparatus, is allowed to provide the
necessary energy for the fieldbus system. The allowed voltage U (or V
or V ) of the associated apparatus is
limited to the range of 14V dc to 24V dc. All other equipment connected to the bus cable has to be passive,
meaning that they are not allowed to provide energy to the system, except to a leakage current of 50 µA for
each connected device. Separately powered equipment needs a galvanic isolation to assure that the
intrinsically safe fieldbus circuit remains passive.
The cable used to interconnect the devices needs to have the parameters in the following range:
i
max
i
max
i
i
oc
i
max
o
oc
i
o
sc
i
o
max
t
o
loop resistance R*:
15 ... 150
/ km
inductance per unit length L*:
0,4 ...
1 mH / km
capacitance per unit length C*:
80 ...
200 nF / km
C* = C*
+ 0.5 C*
, if both lines are floating or
C* = C*
+ C*
, if the screen is connected to one line
Maximum allowed cable length:
CLASS I, ZONE 0 ia
CLASS I, ZONE 1 ib
Length of spur cable:
30 m
30 m
Length of trunk cable:
1 km
5 km
Total length (sum of trunk and spur cables)
1 km
5 km
Length of splice
1 m
1 m
At each end of the trunk cable an approved infallible line termination with the following parameters is suitable:
R = 90 ...100
C = 0 ... 2.2 µF.
One of the allowed terminations might already be integrated in the associated apparatus.
The number of passive devices connected to the bus segment is not limited due to I.S. reasons. If the above
rules are respected, up to the specified total length, the inductance and capacitance of the cable will not impair
the intrinsic safety or the installation.
W
£
£
£
£
£
£
£
£
W
line/line
line/screen
line/line
line/screen
2365061700
ULTRASONICS
SITRANS Probe LU
PROFIBUS PA
CONNECTION DRAWING
23650617
18 / APRIL / 2005
APRIL
18 / 2005
Содержание sitrans PROBE LU
Страница 1: ...Quick Start Manual May 2008 PROBE LU PROFIBUS PA sitrans ...
Страница 18: ...Page EN 16 SITRANS Probe LU PROFIBUS PA QUICK START MANUAL 7ML19985QV81 mmmmm English Notes ...
Страница 34: ...Side DA 16 SITRANS Probe LU PROFIBUS PA KVIKSTART MANUAL 7ML19985QV81 mmmmm Dansk Bemærkninger ...
Страница 50: ...Seite DE 16 SITRANS Probe LU PROFIBUS PA KURZANLEITUNG 7ML19985QV81 new mmmmm Deutsch Notizen ...
Страница 82: ...Página ES 16 SITRANS Probe LU PROFIBUS PA GUÍA PARA LA PUESTA EN MARCHA 7ML19985QV81 new mmmmm Español Notas ...
Страница 98: ...Page FR 16 SITRANS Probe LU PROFIBUS PA MISE EN SERVICE SIMPLIFIEE 7ML19985QV81 new mmmmm Français Notes ...
Страница 114: ...Pagina IT 16 SITRANS Probe LU PROFIBUS PA MANUALE PER L AVVIO RAPIDO 7ML19985QV81 mmmmm Italiano Annotazioni ...
Страница 130: ...Pagina NL 16 SITRANS Probe LU PROFIBUS PA QUICK START HANDLEIDING 7ML19985QV81 mmmmm Nederlands Opmerkingen ...
Страница 146: ...Página PT 16 Sonda LU SITRANS PROFIBUS PA MANUAL DE ARRANQUE RÁPIDO 7ML19985QV81 mmmmm Português Notas ...
Страница 162: ...Sivu SU 16 SITRANS Probe LU PROFIBUS PA PIKAKÄYTTÖOPAS 7ML19985QV81 mmmmm Suomi Huomautukset ...
Страница 178: ...Sida SV 16 SITRANS Probe LU PROFIBUS PA MANUAL FÖR SNABBSTART 7ML19985QV81 mmmmm Svenska Anmärkningar ...