(1) Display and switchover of operating mode
This area provides information on the currently valid operating mode. The following operating
modes can be shown here:
● On (see the APL online help)
● Out of service (see the APL Online Help)
For more information on changing the operating mode, refer to the "Switching operating states
and operating modes" section in the APL Online Help.
(2) High and low scale range for value
PV1
,
PV2
and
PV3
These values provide information on the display range for the bar graph of the process
values
PV1
,
PV2
and
PV3
. The scale range is set in the engineering system with
the
PVxOpScale
parameter; see Display and operating range for process values and limits.
(3) Display of process value
PV1
,
PV2
and
PV3
including signal status
This area indicates the
PV1
,
PV2
and
PV3
value with the associated signal status. The name
of the configured measured value is displayed depending on the
PV1Meas
/
PV2Meas
/
PV3Meas
variable, in this case "Level" for
PV1
and
PV2
, "OOS" (out of service) for
PV3
.
(4) Display of fill time and empty time
PV1
,
PV2
Fill time and empty time are shown in this area if
Feature
bit 6 (activate calculation of fill time/
empty time) is enabled.
With a positive gradient value, a value is calculated for the fill time. With a negative gradient
value, a value is calculated for the empty time.
The calculated times are only shown if the gradient value is outside the deadband
(
DeadTFiEm_PVx
).
(5) Display of auxiliary values
You can use this area to display two auxiliary values that have been configured in the
Engineering System (ES).
(6) Change to second standard view
The second part of the Standard view can be selected here.
(7) Bar graph for the gradient (
PV1
and
PV2
)
This area shows the current gradient value in the form of a bar graph. The visible area in the bar
graph depends on the configuration in the engineering system (ES), see Display and operating
range for process values and limits.
MultiRanger 200
16.1 MR200
SITRANS Library for PCS 7
754
Function Manual, 05/2019, A5E35351976-11
Содержание SITRANS PCS 7
Страница 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Страница 38: ...Functions of the faceplates 2 4 Trend view SITRANS Library for PCS 7 38 Function Manual 05 2019 A5E35351976 11 ...
Страница 190: ...SITRANS LUT400 6 2 PLut400 SITRANS Library for PCS 7 190 Function Manual 05 2019 A5E35351976 11 ...
Страница 320: ...SIPART PS2 PA 8 1 SipPS2PA SITRANS Library for PCS 7 320 Function Manual 05 2019 A5E35351976 11 ...
Страница 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Страница 458: ...SITRANS P PA 11 1 SitrP_PA SITRANS Library for PCS 7 458 Function Manual 05 2019 A5E35351976 11 ...
Страница 542: ...SITRANS FC430 12 2 SiFC43Dr SITRANS Library for PCS 7 542 Function Manual 05 2019 A5E35351976 11 ...
Страница 640: ...SITRANS FC430 PA 13 4 FbFC43PA SITRANS Library for PCS 7 640 Function Manual 05 2019 A5E35351976 11 ...
Страница 676: ...SITRANS LR PA 14 1 SitrLRPA SITRANS Library for PCS 7 676 Function Manual 05 2019 A5E35351976 11 ...
Страница 712: ...SITRANS LR HART 15 1 SitrLRHA SITRANS Library for PCS 7 712 Function Manual 05 2019 A5E35351976 11 ...
Страница 776: ...MultiRanger 200 16 3 Mr200Dia SITRANS Library for PCS 7 776 Function Manual 05 2019 A5E35351976 11 ...
Страница 812: ...SITRANS LU HART 17 1 SitrLuHA SITRANS Library for PCS 7 812 Function Manual 05 2019 A5E35351976 11 ...
Страница 838: ...Driver blocks 18 5 PiSA256H SITRANS Library for PCS 7 838 Function Manual 05 2019 A5E35351976 11 ...
Страница 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...