following values must be set manually (the two limit sensors L2 and L3 not occupied by the
P500 module are always configured manually):
Parameter
Meaning
Lx_DevVar
Selection of monitored process value (the process value must be transferred cyclically
as a 4 to 20 mA signal or HART auxiliary variable)
If
Lx_DevVar
= "NotUsed" is selected, the enables for this limiter (
Lx_AH/WH/WL/
AL_En
) are set to FALSE, and a message is not generated.
Lx_Unit
Unit of monitored process value
Lx_AH/WH/WL/AL_En
Enable monitoring of alarm limit
Lx_AH/WH/WL/AL_MsgEn
Enable message on violation of alarm limit
The
Lx_AlmAct
,
Lx_MonAct
and
Lx_MonTrig
inputs contain the message information read
out of the module and are insignificant if the message configuration is not read out of the
module.
You can monitor the process values (
PV_In
(4 to 20 mA signal),
SV
,
TV
,
QV
) for the following
high and low alarm and warning limits:
●
L1/2/3_AH_Lim
: Limit for high alarm
●
L1/2/3_AL_Lim
: Limit for low alarm
●
L1/2/3_Hyst:
Hysteresis
●
L1/2/3_RespT:
Response time
●
L1/2/3_WH_Lim
: Limit for high warning
●
L1/2/3_WL_Lim
: Limit for low warning
The result of limit monitoring is returned at the interconnectable output parameters:
●
L1/2/3_AH_Act
= 1: Limit for high alarm reached or exceeded
●
L1/2/3_AL_Act
= 1: Limit for low alarm reached or undershot
●
L1/2/3_WH_Act
= 1: Limit for high warning reached or exceeded
●
L1/2/3_WL_Act
= 1: Limit for low warning reached or undershot
Monitoring is always enabled using the input parameters:
●
L1/2/3_AH_En
= 1: Monitoring of the high alarm limits
●
L1/2/3_AL_En
= 1: Monitoring of the low alarm limits
●
L1/2/3_WH_En
= 1: Monitoring of the high warning limits
●
L1/2/3_WL_En
= 1: Monitoring of the low warning limits
The corresponding message is suppressed using the parameters:
●
L1/2/3_AH_MsgEn
= 0: Alarm (high) messages are suppressed
●
L1/2/3_AL_MsgEn
= 0: Alarm (low) messages are suppressed
●
L1/2/3_WH_MsgEn
= 0: Warning (high) messages are suppressed
●
L1/2/3_WL_MsgEn
= 0: Warning (low) messages are suppressed
SITRANS P
10.1 SitransP
SITRANS Library for PCS 7
368
Function Manual, 05/2019, A5E35351976-11
Содержание SITRANS PCS 7
Страница 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Страница 38: ...Functions of the faceplates 2 4 Trend view SITRANS Library for PCS 7 38 Function Manual 05 2019 A5E35351976 11 ...
Страница 190: ...SITRANS LUT400 6 2 PLut400 SITRANS Library for PCS 7 190 Function Manual 05 2019 A5E35351976 11 ...
Страница 320: ...SIPART PS2 PA 8 1 SipPS2PA SITRANS Library for PCS 7 320 Function Manual 05 2019 A5E35351976 11 ...
Страница 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Страница 458: ...SITRANS P PA 11 1 SitrP_PA SITRANS Library for PCS 7 458 Function Manual 05 2019 A5E35351976 11 ...
Страница 542: ...SITRANS FC430 12 2 SiFC43Dr SITRANS Library for PCS 7 542 Function Manual 05 2019 A5E35351976 11 ...
Страница 640: ...SITRANS FC430 PA 13 4 FbFC43PA SITRANS Library for PCS 7 640 Function Manual 05 2019 A5E35351976 11 ...
Страница 676: ...SITRANS LR PA 14 1 SitrLRPA SITRANS Library for PCS 7 676 Function Manual 05 2019 A5E35351976 11 ...
Страница 712: ...SITRANS LR HART 15 1 SitrLRHA SITRANS Library for PCS 7 712 Function Manual 05 2019 A5E35351976 11 ...
Страница 776: ...MultiRanger 200 16 3 Mr200Dia SITRANS Library for PCS 7 776 Function Manual 05 2019 A5E35351976 11 ...
Страница 812: ...SITRANS LU HART 17 1 SitrLuHA SITRANS Library for PCS 7 812 Function Manual 05 2019 A5E35351976 11 ...
Страница 838: ...Driver blocks 18 5 PiSA256H SITRANS Library for PCS 7 838 Function Manual 05 2019 A5E35351976 11 ...
Страница 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...