15.1.8
Template of SitrLRHA
This process tag type is used to connect a Sitrans LR HART with driver blocks to PCS 7.
Note
Since the APL driver blocks
Or08
,
SelST16, Pcs7AnIn
and
FbAnIn
are missing in the
library for licensing reasons, they must be copied into the library before the Sitrans LR HART
template is copied. For this purpose, create a new CFC in the library, open it, and position
the
Or08
,
SelST16, Pcs7AnIn
and
FbAnIn
blocks from the PCS 7 AP Library into the CFC
using drag-and-drop in order for the blocks to be copied into the library. The newly created CFC
can be deleted once this is completed.
The cyclic values are transferred by the PCS 7 standard blocks
Pcs7AnIn
(4 to 20 mA signal)
and
FbAnIn
(HART variables), the acyclic values are transferred by the
PiDr64
block to and
from the device.
The process tag type contains the required interconnections between the blocks mentioned
above. If not all four HART variables are used, the unneeded driver blocks for reading the
values (PV, SV, TV and QV) can be accordingly removed from the template.
The
PV_In
inputs of the
Pcs7AnIn
(4 to 20 mA) and
FbAnIn
(PV, SV, TV, QV) blocks must
be interconnected with the corresponding input word or double word from HW Config for
instantiation of the template. The
Laddr
input of the PiDr64 block (
AcyclicData
) is
configured with the address of the 4 to 20 mA signal (not interconnected!).
The
SlotHart
input receives the slot number of the SITRANS LR module within the analog
input module at the Sitrans LR (
SitrLRHA
) block. The
Feature
bit 2 must be used to configure
whether communication with the module is by means of the HART protocol.
All required information can be found in HW Config.
Note
Correct configuration of the
SlotHart
input is a mandatory requirement and cannot be
checked by the block.
15.1.9
Operator control & monitoring
15.1.9.1
Views of SitrLRHA
Views of the SitrLRHA block
The SitrLRHA block has the following views:
● Standard view of SitrLRHA (Page 702)
● Alarm view (Page 34)
● Limit view of SitrLRHA (Page 706)
SITRANS LR HART
15.1 SitrLRHA
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
701
Содержание SITRANS PCS 7
Страница 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Страница 38: ...Functions of the faceplates 2 4 Trend view SITRANS Library for PCS 7 38 Function Manual 05 2019 A5E35351976 11 ...
Страница 190: ...SITRANS LUT400 6 2 PLut400 SITRANS Library for PCS 7 190 Function Manual 05 2019 A5E35351976 11 ...
Страница 320: ...SIPART PS2 PA 8 1 SipPS2PA SITRANS Library for PCS 7 320 Function Manual 05 2019 A5E35351976 11 ...
Страница 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Страница 458: ...SITRANS P PA 11 1 SitrP_PA SITRANS Library for PCS 7 458 Function Manual 05 2019 A5E35351976 11 ...
Страница 542: ...SITRANS FC430 12 2 SiFC43Dr SITRANS Library for PCS 7 542 Function Manual 05 2019 A5E35351976 11 ...
Страница 640: ...SITRANS FC430 PA 13 4 FbFC43PA SITRANS Library for PCS 7 640 Function Manual 05 2019 A5E35351976 11 ...
Страница 676: ...SITRANS LR PA 14 1 SitrLRPA SITRANS Library for PCS 7 676 Function Manual 05 2019 A5E35351976 11 ...
Страница 712: ...SITRANS LR HART 15 1 SitrLRHA SITRANS Library for PCS 7 712 Function Manual 05 2019 A5E35351976 11 ...
Страница 776: ...MultiRanger 200 16 3 Mr200Dia SITRANS Library for PCS 7 776 Function Manual 05 2019 A5E35351976 11 ...
Страница 812: ...SITRANS LU HART 17 1 SitrLuHA SITRANS Library for PCS 7 812 Function Manual 05 2019 A5E35351976 11 ...
Страница 838: ...Driver blocks 18 5 PiSA256H SITRANS Library for PCS 7 838 Function Manual 05 2019 A5E35351976 11 ...
Страница 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...